OPERATING INSTRUCTIONS
For Electronic Polarity Reversing Control Units
WORKHOLDING AND AUTOMATION
The electronic control-unit provides a selftest cycle, that goes into action as soon as voltage is available.
Three failure messages are possible at the LED-display:
4. Check of Controller and Trouble Shooting:
Symptome
Possible cause
Measures for locating the fault
Solution
Remarks
„Display“
Failure Chuck
Conection from controller to
chuck is broken
Check cable connection
When cable is defective, change it.
Please verifiy the cable diameter
with the instruction manual.
Only to be
performed by
experienced
electrician!
Switch-off
mains supply!
Check plug connection
Clean and dry. Change when bum
marks are present. Use proper
protection
Check slipring body with carbon
brushes
Clean and dry. Change when
bum marks are present. Change
wom Carbon Brushes. Check for
proper sealing and ventilation of
the housing.
Magnetic system defective
Measure coil resistance and
isolation resistance (disconnect
cable at control unit +/-)
Send Magnetic System with Cont-
rols to SAV.
Measure coil resistance and
isolation resistance (disconnect
cable at magnet terminal box)
Send Magnetic System with Cont-
rols to SAV.
Mains voltage variations
bigger than 5% / Phase
shifts in mains.
When step-down transformer is
used, measure the secondary
voltage during first demagneti-
zing pulse
Use isolation transformer with
suitable rating.
Mains power factor compen-
sation unit defective. Check
Cos-Phi.
When required, change compen-
sators.
Is a frequency converter present
in mains?
Set-up a separate mains supply
„Display“
Failure mains
voltage
Mains voltage variations
bigger than 5% / Phase
shifts in mains.
When step-down transformer is
used, measure the secondary
voltage during first demagneti-
zing pulse
Use isolation transformer with
suitable rating.
Mains power factor compen-
sation unit defective. Check
Cos-Phi.
When required, change compen-
sators.
Is a frequency converter present
in mains?
Set-up a separate mains supply
Wrong mains voltage
Check mains voltage according
instruction manual
When required, connect to correct
voltage
Cable diameter to small
Use cable with suitable diameter
according instruction manual
Defective magnetic system
Measure coil resistance and
isolation resistance (disconnect
cable at control unit +/-)
Send Magnetic System with Cont-
rols to SAV.
Measure coil resistance and
isolation resistance (disconnect
cable at magnet terminal box)
Send Magnetic System with Cont-
rols to SAV.