NRT405F901 manual
Chapter 17
Modbus signals
37
Coil status register
Name of signal
Type
Modbus
address
Default
value
Description
RC_Setp_L.NRTBypass
L,1
1
0
Puts the unit in Bypass mode. Reverts
automatically after Bypass time has
elapsed (default=120 min).
RC_Setp_L.NRTShutDown
L,1
2
0
Puts the unit in Shutdown mode.
RC_Setp_L.NRTModbusTwoStop
L,1
3
0
Two stop bits for Modbus communication
RC_Setp_L.NRTDiNC(0)
L,1
4
0
Not used
RC_Setp_L.NRTDi1NC
L,1
5
0
Normally open (NO) or normally closed
(NC) on digital input. 0=NO, 1=NC.
Not used in this model
L,1
6
.
RC_Setp_L.NRTUDi1NC
L,1
7
0
Normally open (NO) or normally closed
(NC) on universal digital input. 0=NO,
1=NC.
Not used in this model
L,1
8
-
RC_Setp_L. NRTDO4NC
L,1
9
1
DO4 NO/NC
RC_Setp_L.NRTDO5NC
L,1
10
1
DO5 NO/NC
RC_Setp_L.NRTDilAct
L,1
11
0
DI1-activation (presence/window)
Economy/Off
RC_Setp_L.NRTMPAct
L,1
12
0
Activation of Mould protection.
RC_Setp_L.NRTTermoModel
L,1
13
0
EEPROM storage of Thermo model
variable (3-point actuator)
RC_Setp_L.NRTMinFanSpeed
L,1
14
1
The fan is run at its minimum speed
setting if the automatic fan control
calculates that the fan can be switched
off.
Not used in this model
-
15
-
RC_Setp_L.NRTComFactoryDefaults
L,1
16
0
Set communication parameters to
factory settings (does not apply to
addresses):
1 = Factory settings (resets to 0)
Содержание NRT405F901