Chapter 17
Modbus signals
42
Name of signal
Type
Modbus
address
Default setting
Description
RC_Setp_R.NRTAIChangeOverLimitL
ow
R,3
80
18°C
Controller switches over to
control of cooling if
change-over temperature is
lower
RC_Setp_R.NRTAIChangeOverLimitHi
gh
R,3
81
28°C
Controller switches over to
control of heating if
change-over temperature is
higher
RC_Setp_R.NRTAi1Comp
R,3
82
0°C
Compensation for analogue
input 1
RC_Setp_R. NRTUi1Comp
R,3
83
0°C
Compensation for universal
input 1
RC_Setp_R.NRTInternalTempComp
R,3
84
0°C
Compensation for internal
room sensor
RC_Setp_R.NRTTempFilterFactor
R,3
85
0.2°C
Filter factor for
temperature on analogue
input
0 = No filter
1 = Max filter
Not used in this model
R,3
86-89
-
RC_Setp_R.NRTThermostatHyst
R,3
90
10
Room hysteresis
RC_Setp_R.NRTComfortSetPDeadBan
d
R,3
91
2
Deadband for Comfort
mode.
RC_Setp_R. NRTComfortSetP
R,3
92
22°C
Setpoint for Comfort mode.
Not used in this model
R,3
93
-
RC_Setp_R.NRTHeatOutputManual
R,3
94
0 %
Manual output heating
output (0…100 %)
RC_Setp_R.NRTCoolOutputManual
R,3
95
0 %
Manual output cooling
output (0…100 %)
RC_Setp_R.NRTRoomTempRemote
R,3
96
-255
Used for remote control of
room temperature. External
Room sensor must be
selected.
RC_SetpExt_R.NRTSetPoint
R,3
284
22°C
Basic setpoint