Chapter 19 BACnet signals
Analogue inputs
Object name
Object ID
Description
Unit
Writeable
RC_Actual_R.NRTRoomTemp
Analog input, 0
Room temperature
°C
No
RC_Actual_R.NRTAIChangeOver Analog input, 1
Change-over temperature
°C
No
RC_Actual_R.NRTAnaIn1
Analog input, 2
Value on analogue input 1
°C
No
RC_Actual_R.NRTUAnaIn1
Analog input, 3
Value on universal analogue
input 1
V
No
Not used in this model
Analog input, 4
No
Analogue values
Object name
Object ID
Description
Unit
Writeable
RC_Actual_R.NRTUAnaOut1
Analog value, 0
Value on universal analogue
output 1
V
No
RC_Actual_R.NRTUAnaOut2
Analog value, 1
Value on universal analogue
output 2
V
No
RC_Actual_R.NRTSetPAdjustment
Analog value, 2
Setpoint adjustment from
internal unit
°C
No
RC_Actual_R.NRTPIDSetP
Analog value, 3
Controller setpoint
°C
No
RC_Actual_R.NRTPIDOutput
Analog value, 4
Controller output
%
No
RC_Actual_R.NRTHeatOutput
Analog value, 5
Heating control
%
No
RC_Actual_R.NRTCoolOutput
Analog value, 6
Cooling control
%
No
Not used in this model
Analog value, 7-8
Yes
RC_Setp_R.NRTUnOccSetPHeat
Analog value, 9
The room heating setpoint
when in unoccupied mode
°C
Yes
RC_Setp_R.NRTUnOccSetPCool
Analog value, 10
The room cooling setpoint
when in unoccupied mode
°C
Yes
Not used in this model
Analog value, 11-12
Yes
RC_Setp_R.NRTHeatOutputManual
Analog value, 13
Manual value heating output
%
Yes
RC_Setp_R.NRTCoolOutputManual
Analog value, 14
Manual value cooling output
%
Yes
RC_Setp_R.NRTRoomTempRemote
Analog value,15
Remote control of room
temperature.
°C
Yes