NRT405F901 manual
Chapter 19
BACnet signals
47
Multistate values
Object name
Object ID
Description
Values
Writeable
RC_Setp_X.NRTHeatOutputSelect
Multistate value, 0
Manual/Auto
heat output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTCoolOutputSelect
Multistate value, 1
Manual/Auto
cool output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTFanSelect
Multistate value, 2
Fan mode select
1=Off
2=Manual speed 1
3=Manual speed 2
4=Manual speed 3
5=Auto
6=Auto 2
7=Auto 1
Yes
Not used in this model
Multistate value, 3
Manual/Auto
forced ventilation
1=Off
2=Manual on
3=Auto
Yes
RC_Setp_X.NRTChangeOverSelect
Multistate value, 4
Manual/Auto
change-over
1=Heating
2=Cooling
3=Auto
Yes
RC_Setp_X.NRTRemoteState
Multistate value, 5
Remote control
unit state
1=Off
2=Economy/Standby
3=Economy/ Standby
4=Presence
6=No remote control
Yes
Device
The
Device
object contains to writeable properties;
Description
and
Location
.
Description
can be 17 characters in length and
Location
can be 33 characters, as long as single byte
character encoding is used.