Configuration sheet (continued)
SERV..
System value Meaning
50
40
Xp V2 (PI, K)
51
240
Reset time V2 (PI, s)
52
1.5
X
sh
V2 (PI, K)
53
+2.0
Degree of intervention for return-temperature limitation at V2 (K/K)
54
5.0
Degree of intervention for flow-rate limitation at V2 (K/min)
55
5
Valve closed delay time for V2 (min)
56
0.20
Minimum opening after delay V2
57
5
Time of disabled temperature and flow-rate monitoring at V2 (min)
58
0.3
Valve position for frost protection V2
59
0.3
Valve position for manual operation V2
60
20
Reference-room temperature (° C)
61
12
Heating limit / heating degree days (° C)
62
0
Heating days (d)
63
0
Heating degree days (° C d)
64
+3
Frost limit (° C)
65
–15
Design temperature (° C)
66
0.50
Curvature factor HK 1
67
0.0
Extraneous heat HK 1 (K)
68
–3
Influence of room-temperature link-up HK 1 (K/K)
69
0
Influence of room-temperature link-up HK 1 (K/K)
70
0.50
Curvature factor HK 2
71
0.0
Extraneous heat HK 2 (K)
72
–3
Influence of room-temperature link-up HK 2 (K/K)
73
0
Influence of room-temperature link-up HK 2 (K/K)
74
75
Max. flow temperature HK 1 (° C)
75
0
Min. flow temperature HK 1 (° C)
76
0
Validity of limitation HK 1
77
75
Max. flow temperature HK 2 (° C)
78
0
Min. flow temperature HK 2 (° C)
79
0
Validity of limitation HK 2
R
–
56
–
7 000458 003