Configuration sheet (continued)
SERV..
System value Meaning
20
–1
Function output I
0
:
21
–1
Function output I
1
:
22
+05
Function output I
2
:
23
+03
Function output I
3
:
24
–1
Function output I
4
:
25
+00
Function output I
5
:
26
–1
Function output I
6
:
27
+07
Function output I
7
:
28
–1
Flow rate configuration
29
1.00
Value of counting pulse
30
10.00
Value of current signal (m
3
/h)
31
0.00
Lower flow-rate limit value (m
3
/h)
32
10.00
Upper flow-rate limit value for heating and domestic hot water (m
3
/h)
33
10.00
Upper flow-rate limit value for heating only (m
3
/h)
34
10.00
Upper flow-rate limit value for domestic hot water only (m
3
/h)
35
90
Upper return-temperature limit value (° C)
36
90
Lower return-temperature limit value (° C)
37
0
Actuation point (° C)
38
0.0
Slope of floating portion
39
90
Return-temperature limit value during domestic-hot-water heating (° C)
40
40
Xp V1 (PI, K)
41
240
Reset time V1 (PI, s)
42
1.5
X
sh
V1 (PI, K)
43
+2.0
for return temperature V1 (K/K)
44
10.0
for flow-rate limitation V1 (K/min)
45
5
Valve closed delay time for V1 (min)
46
0.20
Minimum opening after delay V1
47
5
Time of disabled temperature and flow-rate monitoring V1 (min)
48
0.30
Valve position for frost protection V1
49
0.30
Valve position for manual operation of V1
R
–
55
–