46
EQJW146F001 EN
Appendix
Display reading
Parameter name
Value range (default setting)
Max. flow temperature
5.0 to 150.0 °C (90.0 °C)
When CO1, 2 > F05 - 1: 5.0 to 50.0 °C (50.0 °C)
Four-point characteristic
Press rotary pushbutton
[
Û
]
to set the following parameters:
Outdoor temperature
Flow temperature
Reduced flow temperature
Return flow temperature
Four-point characteristic
Point 1: outdoor temperature
Outdoor temperatures of points 2, 3 and 4 are marked by
squares under the numbers 2, 3 and 4.
–50.0 to +50.0 °C
(pt. 1: –15.0 °C, pt. 2: –5.0 °C, pt. 3: 5.0 °C, pt. 4: 15.0 °C)
When CO1, 2 > F04 - 1
(pt. 1: 5.0 °C, pt. 2: 15.0 °C, pt. 3: 25.0 °C, pt. 4: 30.0 °C)
Four-point characteristic
Point 1: flow temperature
Flow temperatures of points 2, 3 and 4 are marked by squares
under the numbers 2, 3 and 4.
–5.0 to +150.0 °C
(pt. 1: 70.0 °C, pt. 2: 55.0 °C, pt. 3: 40.0 °C, pt. 4: 25.0 °C)
When CO1, 2 > F04 - 1:
(pt. 1: 20.0 °C, pt. 2: 15.0 °C, pt. 3: 10.0 °C, pt. 4: 5.0 °C)
Four-point characteristic
Point 1: reduced flow temperature
Reduced flow temperatures of points 2, 3 and 4 are marked by
squares under the numbers 2, 3 and 4.
–5.0 to +150.0 °C
(pt. 1: 60.0 °C, pt. 2: 40.0 °C, pt. 3: 20.0 °C, pt. 4: 20.0 °C)
When CO1, 2 > F04 - 1:
(pt. 1: 30.0 °C, pt. 2: 25.0 °C, pt. 3: 20.0 °C, pt. 4: 15.0 °C)