EQJW146F001 EN
37
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
09
Flash adaptation
of the flow
temperature
0
All*
CO2 > F09 - 1: only with CO2 > F01 - 1
Function block parameters:
Cycle time: 0 or 1 to 100 min (20 min)
KP (gain): 0.0 to 25.0 (0.0)
11
Four-point char-
acteristic
0
All*
CO2 > F11 - 1: Four-point characteristic, only with CO2 > F08 - 0
CO2 > F11 - 0: Gradient characteristic
12
Control mode
1
All*
CO2 > F12 - 1: Three-step control
Function block parameters:
KP (gain): 0.1 to 50.0 (2.0)
Tn (reset time): 1 to 999 s (120 s)
TV (derivative-action time): 0 s, do not change the value.
TY (valve transit time): 15, …, 240 s (120 s)
CO2 > F12 - 0: On/off control
Function block parameters:
Hysteresis: 1.0 to 30.0 °C (5.0 °C)
Min. ON time: 0 to 10 min (2 min)
Min. OFF time: 0 to 10 min (2 min)
13
Limitation of set
point deviation
for OPEN signal
0
All*
CO2 > F13 - 1: only with CO2 > F12 - 1
Function block parameters:
Max. system deviation: 3.0 to 10.0 °C (3.0 °C)
14
Release HC2 at
input BI2
0
All*
With CO2 > F14 - 1 setting: FG2 has no function
Select:
BI = 1, BI = 0 (BI = 1)
16
Demand
processing
0 to 10 V
Input terminals
11/12
0
All*
CO2 > F16 - 1: demand processing in HC2
Function block parameters:
Lower transmission range: 0 to 150 °C (0 °C)
Upper transmission range: 0 to 150 °C (120 °C)
F Function block number, WE Default setting, Anl System code number
CO4: DHW circuit (systems Anl 1.1–1.3, 1.5, 1.6, 1.9, 2.x, 4.1, 4.5, 11.x)*
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
Storage tank sen-
sor SF1
1
1.1–1.3, 1.5,
1.6, 2.x, 4.1,
4.5, 11.0, 11.2
CO4 > F01 - 0 (not system Anl 11.0): storage tank thermostat, only when
CO4 > F02 - 0
0
1.9, 11.9