44
EQJW146F001 EN
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
06
Send AF1
0
All
CO7 -> F06 - 1:
Function block parameters:
Register number/1 to 4 (1)
07
Receive AF1
0
All
CO7 -> F07 - 1:
Function block parameters:
Register number/1 to 4 (1)
08
Send AF2
0
All
CO7 -> F08 - 1: Analysis active
Function block parameters:
Register number/1 to 4 (2)
09
Receive AF2
0
Not Anl 1.9
CO7 -> F09 - 1:
Function block parameters:
Register number/1 to 4 (2)
10
Send demand in
HC1
0
All
CO7 -> F10 - 1: Send demand
Function block parameters:
Register number/5 to 64 (5)
11
Send demand in
HC2
0
All
CO7 -> F11 - 1:
Function block parameters:
Register number/5 to 64 (5)
13
Send demand
DHW
0
All
CO7 -> F13 - 1: 'Charging temperature boost' (P04) is generated in the PA4
level
Function block parameters:
Register number/5 to 64 (5)
14
Send max. de-
mand
0
All
CO7 -> F14 - 1: the controller already determines internally the maximum
flow set point of its circuit and sends it this value to the primary controllers
15
Receive external
demand in HC1
0
All
CO7 -> F15 - 1: External demand processing in HC1
Function block parameters:
Register number/5 to 64 (5)
16
Receive errors
0
All
CO7 -> F16 - 1: the controller generates the 'External' message as long as the
faults of the other device bus participants exist.
17
Receive external
demand in HC2
0
All
CO7 -> F17 - 1: External demand processing in HC2
Function block parameters:
Register number/5 to 64 (5)
19
Raise return
flow
temperature
0
All
CO7 -> F19 - 1: Return flow temperature limit in HC1 raised when 'DHW
heating active' message is received over the device bus
Function block parameters:
Register number/5 to 64 (32)
20
Send 'DHW
heating active'
0
All
CO7 -> F20 - 1:
Function block parameters:
Register number/5 to 64 (32)
21
Receive release
HC1
0
All
CO7 -> F21 - 1:
Function block parameters:
Register number/5 to 64 (32)