32
33
ENG
ENG
NB!
Due to the potential danger of ther-
mal embrittlement, it is forbidden to use
a PVC-insulated cable as the connection
cable for the sauna climate device.
• The internal connections of the device
are made by means of screw terminals
according to Figure 3 (see page 31)
and Table 1 (see pages 10–11) in this
manual.
• Protective earthing (PE) must be con-
nected to the connection terminal of
the device, with the cross- sectional
area of the cable being at least 2.5
mm2.
• The heater must be powered from
the 380VAC (3-phase) or 230VAC
(1-phase) 50/60 Hz supply circuit
through a control device protected
by an over-current fuse of the size
shown in Table 1 (see pages 10–11).
• If you want to connect the air circu-
lation fan of the device sepa rately
from the heater control device,
the fan must be connected via a
residual-current device. In this case,
the protective earthing (PE) of the
fan supply input terminal of the
sauna climate device must not be
brought into contact with the pro-
tective earthing of the heater sup-
ply input terminal. In this case, use
earthed cables of at least 1.5 mm2 to
power the fan.
• The power cable must enter the
housing of the sauna climate device
so that the water does not flow along
the cable into the electrical connec-
tion box of the housing of the sauna
climate device. The outer insulation
of the cable can only be peeled
off only from the part that is in the
device housing.
• If the connection and installation
cables are higher than 1,000 mm
from the floor of the sauna room or
inside the walls of the sauna room,
they must be able to withstand at
least 170 °C (e.g., SSJ). Electrical
equipment installed higher than
1,000 mm above the floor must be
permitted for use at 125 °C (marking
T125).
• The recommended cross-section
of the connection cable grooves is
given in Table 1 (see pages 10–11).
NB!
The sauna climate device may only be
connected by a professional electrician in
accordance with the applicable regulations!
Optional !
Connecting the fan
directly from the
electric panel if
adjustment from
the control panel is
not recommended.
ELEC
TRIC
AL
C
ONNEC
TION
ELEC
TRIC
AL
C
ONNEC
TION
TEMPERATURE SENSOR
(LOCATION ACCORDING
TO THE MANUFACTURER'S
REQUIRMENTS)
STEAM ROOM
FAN
HEATING
ELEMENTS
CAPTEUR
PORTE
ELECTRIC
PANEL
CONTROL
PANEL
CONTROL UNIT
3x 1.5 Ø
5x 2.5 Ø
3x 1.5 Ø
5x 2.5 Ø