Basic Installation Guide
Mounting M-VUE to an Actuator
Loosen the three captive screws
from the electronics module and
undock the mounting base
Re-attach sensor electronics
module to the sensor
mounting base. At this
point verify the mechanical
indicator displays the correct
position
Install the enclosed O-ring to the
mounting base and attach it to the
top of the actuator. The plate will fit
directly to Saunders actuators with
a separation of 35mm at the top.
Other actuators or distances will
require an additional adapter plate.
The yellow indicator should be
fully visible when the aseptic valve
is OPEN. If additional adjustments
are necessary adjust the height of
the yellow indicator knob until the
OPEN position is visible.
Screw fix the Magnetic Target with
Visual Indication to the actuator.
We recommend any low strength
threadlock adhesive.
After adjustments have been
completed tighten the three captive
screws at the base of the sensor
Connect any air fittings and tube to
the actuator(and M-VUE solenoid if
integral solenoid is fitted)
Note: Supply pressure not to exceed 8 bar (116 PSI)
Once power supply is provided to
M-VUE, it will perform self-check
to indicate valve position. After self
check the LEDs indicate the valve
position and factory settings for
the sensor are unchanged.
Optional Exhaust Port Block
M-VUE can be equipped with an optional
exhaust block if air used by pneumatic
actuator needs to be ported out of a
classified area.
Make sure the O-ring provided with the block
is installed correctly between the pneumatic
case and the exhaust block in order to avoid
any air leakage. Use the three enclosed screws
to secure the block to the case.
35 mm
xx mm
Valve
Sensor