25
www.cranecpe.com
Crane ChemPharma & Energy
DeviceNet
Addressing (DeviceNet Units Only)
This parameter allows the address of the M-VUE sensor to be set. The M-VUE can be addressed from 00 to 63. The DeviceNet sensor is
equipped with LCD screen that will show Address and Baud Rate information.
Important! The M-VUE cannot have the same address as other network equipment, if this occurs, the equipment with the same address will
not work. Once the address is set, the network speed (Baud rate) at which M-VUE will communicate in the network also needs to be set (See
setting network speed/baud rate).
1. Hold the magnetic key over H2 for 3 seconds.
The ring of LED’s will flash green for 2 seconds.
(This indicates Configuration Mode has been accessed.)
2. All LEDs will flash for 2 seconds immediately after P1 will flash green.
Use H1 to select SET on the LCD screen.
-P1 and P6 LEDs will flash green.
3. Use H2 to select the DeviceNet address.
(The ONEs digit will flash.)
4. Use H1 to change the digits (0 to 9).
Use H2 to confirm the desired numeric value.
5. After the “units “digit has been set, the “TENs” digit will flash.
(Waiting to change or confirm the current value.)
6. Use H1 to change the digits (0 to 6).
Use H2 to confirm the desired numeric value.
7. To exit the configuration mode hold the magnetic key over H1 for
more than 3 seconds.
Note: Addressing of MVUE can also be performed remotely during valve
commission form the control system (DCS or PLC)