panel outputs, it activates the fire alarm verification function. The verification operates as 
follows:  the  first  violation  cuts  the  fire  detectors  power  supply  off  for  about  15  seconds. 
The  power-down  results  in  reset  of  the  violated  detectors.  Then,  the  power  supply  is 
restored,  but  the  panel  will  not  control  the  “24H  fire”  zones  for  ten  to  twenty  seconds 
because of the balancing of detectors. Next, the control panel enters the special mode of 
fire detectors control, which lasts about 90 seconds. If a repeated detector violation occurs 
during that time, a FIRE alarm will be triggered. Otherwise, the control panel will go over 
to  the  normal  control  of  “24H  fire”  zones  (duration  of  the  whole  verification  process  is 
approx. 2 min.). The output reacts to the "RESET power supply" function (user function 9). 

29  – power  supply with  RESET  function 

–  the  output  is  designated  to  power  detectors  which 

require a periodical power cut-off until the state memory is cleared. The RESET function is 
activated  from  keypad  through  the  user  function  9  (calling:  [CODE][*][9]). The voltage is 

cut off for time programmed as the output active time. 

30  – TIMER

  – 

the  output  is  controlled  by  the  control  panel  clock;  it  is  activated/deactivated  in  the 

hours indicated by a corresponding TIMER (see: Functions programming TIMERS). 

31  – audible alarm status 

– 

the output signals the audible armed mode. Operation of the output 

can be limited to the selected "list of zones" or partition. 

32  – full arm status

 – 

the  output is only active when all zones/partitions assigned to it are in the 

armed mode. 

33  – ARM/DISARM/CLEAR  ALARM 

– 

the  output  signals  the  particular  system  states  with, 

respectively, one, two, or four pulses 0.16 s each.  

34  – alarm in keypad 

– 

silent alarm signaling in the partition keypad.

  

35  – power supply on armed mode

 

– it functions similarly to the ARM STATUS output, but it is 

activated  right  after  "exit  delay"  starts,  not  after  changeover  from  the  exit  delay  to  the 
armed  mode  (it  can  be  used,  for  example,  as  indicator  or  power  supply  output  for 
microwave detectors in spaces where people stay). 

36  – signalling: LED 

– the output can control a LED to indicate the following statuses: 

-

 

off – control panel disarmed 

-

 

steady light – control panel armed  

-

 

blinking light – the control panel armed, there was alarm or trouble  

Note:

  If  in  the  armed  mode  any  zones  are  violated  in  the  system,  the  LED  will  be 

blinking and will only change to steady light after the violation ends.

  

37  – signalling:  relay 

– 

the  output  can  control  a  relay.  The  output  becomes  active  after  arming, 

and inactive after an alarm is triggered, a trouble occurs, or the system is disarmed. 

Note:

 

If  in  the  armed  mode  any  zones  are  violated  in  the  system,  the  output  will 
become active after the violation ends. 

38  – 

not used

 

 

(do not program).

 

39  – no  guard  code 

– 

the  output  is  activated  by  a  timer  programmed  as  the  partition  control 

TIMER, unless a guard code is entered within the timer specified time. 

40  – service  mode  status 

– 

the  output  is  activated  if  the  control  panel  service  mode  has  been 

called from any keypad.

  

41  – battery low status 

– the output, which state is updated after each battery voltage test.

  

Partitions 

A new partition is created when at least one zone is assigned to it. The CA-6 permits creating 
of  two  partitions  to  which  any  outputs,  telephone  numbers  and  pager  messages  can  be 
assigned, and thus enables two alarm systems to be built on the basis of one CA-6 control 
panel.  The  partitions  can  be  controlled  from  a  keypad  (access  codes  assigned  to  the 
partitions)  as  well  as  by  means  of  control  zones.  Both  partitions  can  be  controlled  at  the 
same time. 
Because  the  sirens  connected  to  the  outputs  can  be  activated  by  selected  zones,  the 
assignment of zones to partitions will define which codes can clear alarm on particular sirens. 

Содержание CA-6-P

Страница 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Страница 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Страница 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Страница 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Страница 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Страница 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Страница 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Страница 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Страница 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Страница 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Страница 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Страница 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Страница 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Страница 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Страница 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Страница 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Страница 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Страница 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Страница 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Страница 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Страница 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Страница 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Страница 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Страница 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Страница 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Страница 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Страница 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Страница 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Страница 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Страница 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Страница 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Страница 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Страница 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Страница 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...