Satel CA-6-P Скачать руководство пользователя страница 22

20 

SATEL 

Installer Manual 

 

the battery "-". Connecting the common ground of the device to the battery "-" 
will  result  in  faulty  operation  of  the  charging  current  limiter,  which  will 
eventually lead a quick discharge of the battery, or may even cause damage to 
the control panel.  

Connections of Telephone Line 

If  the  control  panel  telephone  communicator  is  used  in  the  alarm  system  (for  monitoring, 
messaging or remote programming), it is necessary to connect telephone line to the control 
panel. It should be led to a connector situated on the right side of the printed board. In order 
to  ensure  proper  messaging, 

the  control  panel  must  be  directly  connected 

to  the  line

 

(terminals  designated  as  TIP  and  RING),  and  any  other  devices  (telephone,  telefax)  –  after 
the  control  panel  (terminals  designated  as  T-1  and  R-1).  Such  a connection  will  make  it 
possible  for  the  control  panel  to  fully  engage  the  line  for  the time  of  calling,  which  prevents 
the messaging function from being blocked by lifting the handset. Additionally, the telephones 
connected after the control panel do not signal the dialing by the control panel. 

The  telephone  line

  must  be  a  four-wire  line  so  that  the  control  panel  can  be  connected 

before the other devices (telephone, telefax, etc.). 

Notes: 

 

Do not send telephone signals and alarm system signals by one multicore cable. This may 
result in damage to the system in case of a high-voltage punch-through from the telephone 
line. 

 

Telephone  terminals  of  the  panel  should  be  connected  to 

PSTN  (analog)  lines  only

Connecting the telephone circuit directly to digital network (e.g. ISDN) will cause damage 
to the equipment. 

 

The  system  installer  should  give  the  necessary  information  on  the  way  of  connection 
control panel to telephone network to the user. 

Connection of Voice Synthesizer 

Where  the  function  of  alarm  messaging  with 
voice  announcements  is  used,  a  voice 
synthesizer must be connected to the control 
panel.  The  CA-6  interfaces  with  the  SM-2 
synthesizer produced by SATEL. 
The synthesizer socket (designated as: SM-2 
VOICE SYNTHESIZER) is located at the right 
side  of  PCB,  between  telephone  line 
connector  and  low-current  output  sockets. 
The  SM-2  synthesizer  should  be  directly 
plugged  into  this  connector.  It  is  fitted  with 
minijacks  for  playback  of  the  message  and 
monitoring of the telephone line. 
 

Connection of power supply  

The  control  panel  is  permanently  connected  to  the  mains  supply  source.  Hence,  before 
making  the  connections  it  is  necessary  to  familiarize  with  the  electric  system  in  the  facility. 
For  powering  the  control  panel  choose  the  circuit  which  is  always  live.  The  power  supply 
circuit should be protected with a proper fuse. 

common ground 

low-frequency signal 

triggering 

teltphone line monitoring 

+ power supply (12 V) 

panel board 

Fig. 13. Arrangement of signals on SM-2 

voice synthesizer connectors. 

Содержание CA-6-P

Страница 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Страница 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Страница 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Страница 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Страница 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Страница 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Страница 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Страница 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Страница 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Страница 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Страница 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Страница 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Страница 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Страница 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Страница 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Страница 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Страница 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Страница 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Страница 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Страница 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Страница 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Страница 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Страница 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Страница 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Страница 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Страница 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Страница 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Страница 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Страница 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Страница 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Страница 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Страница 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Страница 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Страница 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...

Страница 35: ...n telephone line public telephone line voice synthesizer see p 20 power supply outputs low current programmable outputs see p 19 programmable zones description of detectors connection see p 16 CTL inp...

Страница 36: ...ed p 12 it requires a new cable now p 12 The schematic view of the CA 6 main board has been changed p 12 and 33 The figure of connection of the detectors to the control panel has been changes to a new...

Отзывы: