Satel CA-6-P Скачать руководство пользователя страница 17

CA-6 

SATEL 

 

15 

 

COM +KPD DATA CLK

Z1

COM

Z2

+KPD CLK

Z1

Z2

DATA

COM

CTL

Z2

D C B

A

CA-6 KLED

keypad 

backlight

Control panel mainboard

keypad

Zone 7

Zone 8

 

Fig. 4. Connection of keypad to control panel. 

The

 

DCBA keypad

 jumpers

 determine the address which is an additional tamper protection. 

The pins D and A are shorted by default; it is possible to change the address (see: FS111, 
FS124).  The  panel  does  not  accept  addresses  of  the  „all  closed”  and „all  open”  type 
addresses. The address is stored in the panel EEPROM (non-volatile) memory, together with 
the other system parameters. 
The

 

keypad

  Z1  and  Z2

 

terminals

  permit  connecting  any  detectors.  They  are  supported  by 

the control panel in the same way as the mainboard zone inputs. The keypad Z1 terminal is 
treated as zone 7, Z2 – as zone 8. 

Provision is made for connecting additional keypads

 (in parallel with the first one). Each 

keypad  should  be  connected  to  the  control  panel  by  means  of  a  separate  cable. 

The

 

address of all keypads should be identical, the zone 7 and 8 can only be used in 

one of them

, elsewhere they should be left open (nothing is to be connected). 

There are two types of keypads designed to work together with the CA-6 control panel. All of 
them  should  be  connected  in  the  way  shown  in  Fig.  4  for  the  CA-6 KLED  keypad.  For 
description of the CA-6 KLED-S terminals, see the figure below. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 5. View of the CA-6 KLED-S keypad board. 

WIRE CONNECTION

 

TAMPER CONTACT 

KEYPAD ADDRESS

 

BUZZER

 




Z2  COM  Z1 

KPD CLK DTA

 

TERMINAL DESCRIPTION

 

KEYPAD 

CONTROL PANEL 

KPD

 

+KPD 

DTA

 

DATA 

CLK 

CLK 

COM 

COM 

Z1 – to 

detector 

Additional system 

zones 

Z2 – to 

detector 

 

 Z2  COM   Z1 

KPD

 

  

CLK

 

  

DTA 

Содержание CA-6-P

Страница 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Страница 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Страница 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Страница 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Страница 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Страница 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Страница 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Страница 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Страница 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Страница 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Страница 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Страница 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Страница 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Страница 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Страница 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Страница 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Страница 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Страница 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Страница 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Страница 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Страница 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Страница 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Страница 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Страница 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Страница 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Страница 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Страница 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Страница 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Страница 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Страница 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Страница 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Страница 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Страница 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Страница 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...

Страница 35: ...n telephone line public telephone line voice synthesizer see p 20 power supply outputs low current programmable outputs see p 19 programmable zones description of detectors connection see p 16 CTL inp...

Страница 36: ...ed p 12 it requires a new cable now p 12 The schematic view of the CA 6 main board has been changed p 12 and 33 The figure of connection of the detectors to the control panel has been changes to a new...

Отзывы: