Satel CA-6-P Скачать руководство пользователя страница 18

16 

SATEL 

Installer Manual 

 
The  spring  on  the 

tamper  contact

  must  cling  to  the  mounting  surface  so  that  the  contact 

opens at any attempt to pull off the keypad from the wall. The keypad 

tamper contact

 has no 

connection with the system tamper circuit. Its state is defined by the control panel, based on 
the data received from the keypad. In case two keypads are connected in parallel, the control 
panel  will  detect  tampering  when  both  contacts  are  open.  When  the  control  panel  is  in  the 
service  mode,  the  tamper  contact  and  the  keypad  address  are  not  controlled.  Should  the 
panel  alarm  at  the  moment  of  exiting  the  service  mode,  it  would  mean  an  incorrectly 
programmed address, or opening of the tamper contact. 

Connection of detectors 

The CA-6 can operate with detectors of any type. Each zone of the control panel can work in 
the  configuration  NC,  NO,  EOL,  2EOL/NO,  2EOL/NC.  When  the  zone  works  in  an  EOL 
configuration, a 2.2 k

 resistor should be used to make the detector circuit. In case of 2EOL 

configuration,  the  detector  circuit  is  closed  by  two  1.1 k

  resistors.  This  type  of  zones 

enables the status of detector and its tamper contact to be monitored at the same time. 
The  detectors  may  be  supplied  from  any  of  the  electronically  protected  outputs  (OUT1  to 
OUT3).  The  output  should  be  programmed  as  the  "POWER  SUPPLY  OUTPUT"  (function 
number 27). The use of OUT3 is suggested. 
Separation  of  the  detector  power  supply  ground  and  the  line  ground  makes  it  possible  to 
eliminate the effect of wiring resistance. Assuming that the wire is rather short, and only one 
detector is connected to it, the installation can be simplified by using one wire for the power 
supply  ground  (GND)  and  the  signaling  ground.  The  NO  and  NC  detectors  in  2EOL 
configuration are connected in the same way, it is only important to correctly indicate to the 
control panel, what type of detector is connected to the zone input (2EOL/NO or 2EOL/NC). 
The  figures  below  only  show  how  the  alarm  relay  outputs  should  be  connected.  Proper 
connection of the detectors will require that power supply (COM, 12 V) be provided and TMP 
terminals (tamper contact) of EOL or NO/NC detectors be connected to the tamper circuit. 
 

 

NC

NC

TMP

COM 12V

NC

TMP

COM OUT3

DTA

CLK

CTL

COM

Z1

Z2

Z3

COM

Z4

KPD

+

COM

CA-6

 

Fig. 6. Example of connecting NC type detector to control panel (NO type detector is to be 

connected in the same way). 

 

Содержание CA-6-P

Страница 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Страница 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Страница 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Страница 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Страница 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Страница 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Страница 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Страница 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Страница 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Страница 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Страница 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Страница 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Страница 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Страница 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Страница 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Страница 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Страница 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Страница 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Страница 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Страница 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Страница 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Страница 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Страница 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Страница 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Страница 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Страница 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Страница 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Страница 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Страница 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Страница 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Страница 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Страница 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Страница 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Страница 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...

Страница 35: ...n telephone line public telephone line voice synthesizer see p 20 power supply outputs low current programmable outputs see p 19 programmable zones description of detectors connection see p 16 CTL inp...

Страница 36: ...ed p 12 it requires a new cable now p 12 The schematic view of the CA 6 main board has been changed p 12 and 33 The figure of connection of the detectors to the control panel has been changes to a new...

Отзывы: