ACCO
SATEL
53
−
tamper of keypad;
−
loss of communication with the terminal (no terminal).
7.6 Module factory settings
The below described settings refer to a new module. The S
ET DEFAULT
button available in the
M
ODULES LIST
window will not restore all the factory settings of the module. Only the settings
available in the M
ODULES LIST
window will be restored. The user list, time schedules and
event log, which were saved to the module memory, will be retained without changes.
Module
All the module related options and functions are disabled.
Module inputs
Input 1: Door status control. NO type. Sensitivity: 50 ms.
Input 2: Unlock button. NO type. Sensitivity: 50 ms.
Input 3: Door unblocking. NO type. Sensitivity: 50 ms.
Input 4: Unused. NC type. Sensitivity: 50 ms.
Input 5: Unused. NC type. Sensitivity: 50 ms.
Module outputs
Output 1: Forced entry. 5 invalid attempts. Operation time: 10 seconds.
Output 2: Long open door. No terminal presence. Operation time: 10 seconds.
Door
Access time: 5 seconds.
Door open time: 20 seconds.
Other functions and options are disabled.
LCD keypad
Time format on LCD keypad: hh:mm
Other options are disabled.
Backlight A/B
Auto.
Access method
Card or code.
Users
"Administrator", ID number 00001, having the A
DMINISTRATOR
and C
HANGE CODE
rights and
using the code 12345.
8. Specifications
8.1 ACCO-KP-PS / ACCO-KPWG-PS module
Supply voltage .................................................................................................... 18 V AC ±10%
Power supply output voltage, rated ................................................................... 12 V DC ±15%
Power supply output current .............................................................................................. 1.2 A
Maximum current consumption ...................................................................................... 110 mA