1. Turn the power to the unit “On”. Red LED pilot light should illuminate at 8 sec. intervals

2. Open door to the hold open point. The door should hold open. Manually pull door out of hold open and release. Door should close

3. Open door to the hold open position. Depress (maintained type) On/Off “test switch” button on the power supply board. Door should close

4. Depress On/Off test switch again. Open door to the hold open position. Inducing smoke into the smoke detector chamber assembly will bring the unit 
  into alarm. The red LED will be continuously illuminated and the door will close. After clearing the smoke chamber, reset unit as follows

Checkout Procedure

1. 

Remote Reset:

 Cycle main power by turning the facility main power supply OFF then ON. 

  NOTE: If there are other units connected to the same power supply those doors will close. 
  They will have to be reopened returning them to the hold open position

2. 

Local Reset:

 Insert a small flat head screwdriver through the cover and into the slotted 

  light tube on the smoke detector as shown. Turn screwdriver slightly (about 1/8 turn)
 

clockwise

 until hitting stop and hold for 2 seconds until the Red LED turns OFF. 

 

WARNING: Do not force past the stop. Doing so may damage the smoke detector

Once the detector is reset and the smoke has cleared, the detector’s Red LED should flash 
once every 8 seconds. The door(s) should hold open now

Resetting Instructions

SARGENT recommends cleaning smoke detectors at least every six months. The frequency of cleaning will depend upon local ambient conditions

The smoke detector in this door closer-holder has been enhanced with a feature that detects when a smoke-sensing chamber requires cleaning 
due to dirt and dust. The need for cleaning is indicated by the flashing of the Red LED light once per second

• 

Normal Supervisory Operation

 — Red LED flashes once every 8 seconds

• 

Dirty Chamber, needs cleaning

 — Red LED flashes once every second

• 

Smoke Detection

 — Red LED is continuously illuminated

To clean the smoke detector assembly, follow the instructions below:

NOTE: Before servicing the system, notify the proper authorities
that the smoke detector system is undergoing maintenance
and will be temporarily out of service. Disable the zone undergoing
maintenance to prevent unwanted alarms

Smoke Detector Maintenance

•  Remove detector cover and screen assembly using a standard screwdriver. Turn the screwdriver in the cover slot to loosen the cover and carefully 
  rock the cover back and forth until it snaps out of place. See slot location above

•  Inspect chamber for particles and dust. Vacuum the screen, cover, and photo chamber. Then use clean, compressed air to loosen and blow out
  any remaining debris

•  Before reassembling the detector, be sure all parts are free of dust and debris

•  Replace cover and screen, aligning cover snaps, press cover onto chamber until it snaps into place

•  Measure and record the test voltage at test points 

RP1 and RP2

 (see above). If the smoke detector is operating normally and was cleaned

  effectively, the test voltage will be 

greater than .90VDC and less than 1.58VDC

. The test voltage will increase with dust accumulation in the

  smoke sensing chamber. A difference in test voltages over time will provide an indication of dust accumulation

•  Enable system and inform proper authorities system is operational

RP2 test point

RP1 test point

Slot for screwdriver
To remove cover

Cover and 
screen

Chamber

Slotted light tube (Red LED)

Содержание 2900 Series FIREGUARD

Страница 1: ...ION TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE 2 INSTALLER MUST BE A TRAINED EXPERIENCED SERVICE PERSON 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG Wiring 12 Units with and without 9 Companion Unit 9 Companion Unit If required Field wiring by others Wire nut On Off Test switch Yellow Red Black Yellow Black Black Term...

Страница 2: ... for remote detector interconnect applications Terminals 8 9 and 10 may be field configured to a dry form contact by cutting jumper between terminal 11 and 12 Terminal 10 is Common 9 is N C and 8 is N O If this is done Aux is lost solenoid power must be supplied by a separate source Terminals 15 and 4 provide interconnections to other detectors See diagram Pg 4 Up to five smoke detectors may be in...

Страница 3: ...a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fol...

Страница 4: ...5 4 10 Remote Detector N O C Relay 4 Use terminals 4 and 15 to wire detectors in parallel See 1 2 and 3 Use terminal 10 to signal remote detectors with relay contact only See 4 and 5 Five detectors maximum Accessory wire pack 63 3212 needed for unit interconnection ...

Страница 5: ...ousing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 Earth ground to track green wire 24VDC 0 15A Max to external alarm Power Supply Board 1 2 Alarm Circuit Trouble Circuit EOL RES Alarm Panel 24VDC Solenoid 24VDC 0 15A Max to external alarm 4 3 2 1 5 6 7 11 10 9 8 12 13 14 1 2 Power Supply Board 15 4 3 2 1 5 6 7 1...

Страница 6: ...ical data sheet Do not overload circuits 5 Wires are added to header housing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 24VDC 0 15A Max to external alarm bell horn etc Power Supply Board 1 2 24VDC Latch 4 3 2 1 5 6 7 11 10 9 8 12 13 14 Connect to power source 24VAC DC or 120VAC Power supply board and power sourc...

Страница 7: ...ay not reach the smoke detector and alarm it A detector may not detect a fire developing on another level of a building For this reason detectors should be located on every level of a building Smoke detectors have sensing limitations Photoelectric detectors sense smoldering fires better than flaming fires Ionization detectors offer a broad range of fire sensing capability but they are better at de...

Страница 8: ...oor stop Rotate cam until switch roller is on lower section of cam and approximately 1 32 from bottom of incline Cam should be positioned so when door closes roller on switch will ride up incline of cam operating the switch Tighten one set screw in cam with hex key and pull door closed 4 Pull door open to desired hold open position When switch roller travels down to bottom of incline door closer w...

Отзывы: