background image

7

A7408B

!

WARNING

!

These fire protection devices require correct wiring
to function. It is the responsibility of the purchaser
to provide correct wiring installation. SARGENT
accepts no responsibility for incorrect wiring.
Devices wired incorrectly may be damaged and
this is not covered under warranty.

Life safety devices including door release devices
require correct positioning and appropriate 
selection for the required task. It is the responsibility
of the purchaser to select appropriate hardware
and provide professional installation. It is the
responsibility of the purchaser to insure that NFPA
and other applicable fire codes are met. Door
release devices function properly only if the door
is free to close. SARGENT accepts no responsibility
for incorrect installation of its equipment.

Smoke detectors will not work without power. AC
or DC powered smoke detectors will not work if
the power supply is cut off for any reason.

All high voltage wiring should be undertaken by a
qualified professional licensed electrician. It is the
responsibility of the purchaser to insure that
installation meets all applicable local and national
electrical codes.

Smoke detectors will not sense fires which start
where smoke does not reach the detectors.
Smoke from fires in chimneys, in walls, on roofs or
on the other side of closed doors may not reach
the smoke detector and alarm it.

A detector may not detect a fire developing on
another level of a building. For this reason, detectors
should be located on every level of a building.

Smoke detectors have sensing limitations.
Photoelectric detectors sense smoldering fires
better than flaming fires. Ionization detectors offer
a broad range of fire-sensing capability, but they
are better at detecting fast, flaming fires than slow
smoldering fires. Because fires develop in different
ways, and are often unpredictable in their growth,
neither type of detector is always best, and a given
detector may not always provide warning of a fire.
In general, detectors cannot be expected to provide
warnings for fires resulting from inadequate fire
protection practices, violent explosions, escaping
gas, improper storage of flammable liquids like
cleaning solvents, other safety hazards, or arson.
Smoke detectors used in high air velocity conditions
may fail to alarm due to dilution of smoke densities
created by such frequent and rapid air exchanges.
Additionally, high air velocity environments may
create increased dust contamination, demanding
more frequent maintenance.

Smoke detectors do not last forever. Even though
detectors are made to last over 10 years, these
components could fail at any time. Therefore, test
your smoke detector system per NFPA 72E at
least semiannually. Clean and take care of your
smoke detectors regularly. Taking care of the fire
detection system you have installed will measurably
reduce your liability risks.

Содержание 2900 Series FIREGUARD

Страница 1: ...ION TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE 2 INSTALLER MUST BE A TRAINED EXPERIENCED SERVICE PERSON 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG Wiring 12 Units with and without 9 Companion Unit 9 Companion Unit If required Field wiring by others Wire nut On Off Test switch Yellow Red Black Yellow Black Black Term...

Страница 2: ... for remote detector interconnect applications Terminals 8 9 and 10 may be field configured to a dry form contact by cutting jumper between terminal 11 and 12 Terminal 10 is Common 9 is N C and 8 is N O If this is done Aux is lost solenoid power must be supplied by a separate source Terminals 15 and 4 provide interconnections to other detectors See diagram Pg 4 Up to five smoke detectors may be in...

Страница 3: ...a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fol...

Страница 4: ...5 4 10 Remote Detector N O C Relay 4 Use terminals 4 and 15 to wire detectors in parallel See 1 2 and 3 Use terminal 10 to signal remote detectors with relay contact only See 4 and 5 Five detectors maximum Accessory wire pack 63 3212 needed for unit interconnection ...

Страница 5: ...ousing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 Earth ground to track green wire 24VDC 0 15A Max to external alarm Power Supply Board 1 2 Alarm Circuit Trouble Circuit EOL RES Alarm Panel 24VDC Solenoid 24VDC 0 15A Max to external alarm 4 3 2 1 5 6 7 11 10 9 8 12 13 14 1 2 Power Supply Board 15 4 3 2 1 5 6 7 1...

Страница 6: ...ical data sheet Do not overload circuits 5 Wires are added to header housing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 24VDC 0 15A Max to external alarm bell horn etc Power Supply Board 1 2 24VDC Latch 4 3 2 1 5 6 7 11 10 9 8 12 13 14 Connect to power source 24VAC DC or 120VAC Power supply board and power sourc...

Страница 7: ...ay not reach the smoke detector and alarm it A detector may not detect a fire developing on another level of a building For this reason detectors should be located on every level of a building Smoke detectors have sensing limitations Photoelectric detectors sense smoldering fires better than flaming fires Ionization detectors offer a broad range of fire sensing capability but they are better at de...

Страница 8: ...oor stop Rotate cam until switch roller is on lower section of cam and approximately 1 32 from bottom of incline Cam should be positioned so when door closes roller on switch will ride up incline of cam operating the switch Tighten one set screw in cam with hex key and pull door closed 4 Pull door open to desired hold open position When switch roller travels down to bottom of incline door closer w...

Отзывы: