4-8
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifications (7)
MODEL NAME
W-2WAY ECO-i Capacity Control Outdoor Unit <26 horsepower>
GENERAL MODEL No.
SPW-WC2605DXHN8
COMPONENT OUTDOOR UNIT
SPW-C1405DXHN8
SPW-C0905DXHN8
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz
380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling capacity
kW (BTU / h)
73.0 (249,100)
Heating capacity
kW (BTU / h)
81.5 (278,100)
COP
Cooling standard
–
3.44
Heating standard
–
3.88
Heating / Cooling ave.
–
3.66
UNIT DIMENSIONS
Height
mm (in.)
1887 (74
-
9 / 32)
Width
mm (in.)
1880 (74)
Depth
mm (in.)
890 (Ceiling dimension) (+60)
(35-1 / 32) (+2 - 3 / 8)
Net weight
kg (lbs.)
345 (760)
295 (650)
Color (Munsell code)
Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Cooling
Running amperes
A
35.4
33.6
32.4
Power input
kW
21.2
21.2
21.2
Power factor
%
91
91
91
Heating
Standard
Running amperes
A
35.1
33.3
32.1
Power input
kW
21.0
21.0
21.0
Power factor
%
91
91
91
Low temp. Power input
kW
23.2
23.2
23.2
Starting amperes
A
96
98
100
COMPRESSOR
Type - Q'ty
Hermetic type x 3
Hermetic type x 2
Motor output
kW
3 + 4.5 x 2
3 + 3.75
Refrigeration oil
Type
FV68S (Ether oil)
Charge amount
L
5.9
4.9
Crankcase heater
W
25 + 32 x 2
25 + 32
Capacity control
%
–
Refrigerant amount at shipment
kg
R410A - 13.0
R410A - 12.0
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Tube with plate fins
FAN DEVICE
Type - Q'ty
Propeller fan x 1
Propeller fan x 1
Air circulation
m
3
/ min
220
160
External static pressure
Pa
0
0
Motor output (No. of poles)
kW
0.7 (8P)
0.7 (8P)
Protective devices
High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Gas tube
mm (in.)
ø28.58 (1-1 / 8) (Brazing)
ø22.22 (7 / 8) (Brazing)
Liquid tube
mm (in.)
ø12.7 (1 / 2) (Flare nut)
ø9.52 (3 / 8) (Flare nut)
Balance tube
mm (in.)
ø6.35 (1 / 4) (Flare nut)
Drain port
–
External air temperature operation range
°C
Cooling: -10 ~ 43 °C (DB)
Heating: -20 ~ 15 °C (WB)
Operation sound (Hi)
dB-A
63.0 (Quiet mode: 60.0)
Primary accessories
Connection tubing
(ø28.58)
Connection tubing
(ø22.22)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
* Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Cooling: Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating [standard]: Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.)
(Heating [low temp.]: Indoor intake air temp. 20°C DB / 15°C WB or less. Outdoor intake air temp. 2°C DB / 1°C WB.)
Содержание ECO G SPW-GU055XH
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 146: ......
Страница 198: ......
Страница 200: ...6 2 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 1 Electric Wiring Diagram SPW C0705DXHN8 ...
Страница 201: ...6 3 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0705DXHN8 ...
Страница 202: ...6 4 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 2 Electric Wiring Diagram SPW C0905 C1155DXHN8 ...
Страница 203: ...6 5 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0905 C1155DXHN8 ...
Страница 204: ...6 6 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 3 Electric Wiring Diagram SPW C1305 C1405DXHN8 ...
Страница 205: ...6 7 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C1305 C1405DXHN8 ...
Страница 206: ...6 8 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 1 Electric Wiring Diagram SPW GU055 075 105XH ...
Страница 207: ...6 9 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 2 Schematic Diagram SPW GU055 075 105XH ...
Страница 208: ......
Страница 242: ......