2-5
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
3: If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1 rank for the
gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following page.)
4:
If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the
size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 28 kg
Max. additional charge for 2 outdoor units: 50 kg
Max. additional charge for 3 outdoor units: 60 kg
Table 1-2 Refrigerant Charge Amount at Shipment (for outdoor unit)
SPW-C0705DXHN8
SPW-C0905DXHN8
SPW-C1155DXHN8
SPW-C1305DXHN8
SPW-C1405DXHN8
12 kg
12 kg
12 kg
13 kg
13 kg
Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 1-3 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size
Liquid tubing size
Amount of refrigerant
charge/m (g/m)
Required amount of charge = (Amount of refrigerant charge per meter of
each size of liquid tube × its tube length) + (...) + (...)
ø6.35
26
*Always charge accurately using a scale for weighing.
*If the existing tubing is used, and the amount of on-site additional
refrigerant charge exceeds the value listed below, then change the size
of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit : 28 kg
Max. additional charge for 2 outdoor units: 50 kg
Max. additional charge for 3 outdoor units: 60 kg
ø9.52
56
ø12.7
128
ø15.88
185
ø19.05
259
ø22.22
366
Table 1-4 System Limitations
Max. No. allowable connected outdoor units
3 *²
Max. capacity allowable connected outdoor units
135 kW (48 hp)
Max. connectable indoor units
40 *¹
Max. allowable indoor/outdoor capacity ratio
50 – 130 %
*1: In the case of 22 hp (type 61.5 kW) or smaller units, the number is limited by the total capacity of the connected indoor units.
*2: Up to 3 units can be connected if the system has been extended.
Содержание ECO G SPW-GU055XH
Страница 2: ...i ...
Страница 3: ...ii ...
Страница 146: ......
Страница 198: ......
Страница 200: ...6 2 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 1 Electric Wiring Diagram SPW C0705DXHN8 ...
Страница 201: ...6 3 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0705DXHN8 ...
Страница 202: ...6 4 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 2 Electric Wiring Diagram SPW C0905 C1155DXHN8 ...
Страница 203: ...6 5 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C0905 C1155DXHN8 ...
Страница 204: ...6 6 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit 3 Electric Wiring Diagram SPW C1305 C1405DXHN8 ...
Страница 205: ...6 7 Electrical Data 1 2 3 4 5 6 7 8 1 Outdoor Unit Schematic Diagram SPW C1305 C1405DXHN8 ...
Страница 206: ...6 8 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 1 Electric Wiring Diagram SPW GU055 075 105XH ...
Страница 207: ...6 9 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit 2 Schematic Diagram SPW GU055 075 105XH ...
Страница 208: ......
Страница 242: ......