System Design
6. Sound-proofing measures
D-30
Table 1. Sound-proofing calculation sheet (filled-in example)
Frequency
Hz 63 125 250 500 1000
2000
4000
8000
From the operating sound characteristics diagram in the outdoor unit manual
1) Operating sound of outdoor
unit
dB
69 66 62 59 56 49.5 45 41.5
From distance attenuation
2) Distance attenuation
dB
From Fig. 1, attenuation of unit operating sound = -22
Fig. 2, Refraction attenuation, sound path difference
δ
= A + B – d = 0.5
3) Refraction attenuation
dB
-
3.5
-
5
-
6.5
-
9
-
12
-
15
-
18
-
21
Fig. 6, Additional sound due to reflections (wall)
4) Additional sound from
reflections (wall surface)
dB
By calculation or the simplified method, the maximum value of the two
combined sounds is +3
Fig. 7, Addition sound due to reflection (ground surface)
5) Additional sound from
reflections (ground surface)
dB
By calculation or the simplified method, the maximum value of the two
combined sounds is +3
6)
Subtotals
dB 49.5 45 39.5 34 28 18.5 11 4.5
Conversion factors for A weighting
7) Overall A-weighting correction
factors
dB
-
26
-
16
-
9
-
3
0 +1 +1
-
1
8)
A
weighting
dB(A)
23.5 29 30.5 31 28 19.5 12 3.5
When the calculations of Table 1 are completed, the overall A weighting can be calculated.
31 30.5 29 28 23.5
Difference = 0.5
(31 + 2.7)
33.7
Difference = 4.7
(33.7 + 1.2)
34.9
Difference = 6.9
35.95 30.0
(34.9+0.8)
35.7
Difference = 5.95
Difference = 12.2
(35.95+0.95)
35.7 + 0.25 = 35.95 dB
=36.9
(8) Sound-proofing calculation sheet (example)
Frequency
Hz 63 125 250 500 1000
2000
4000
8000
From the operating sound characteristics diagram in the outdoor unit manual
1) Operating sound of outdoor
unit
dB
Distance attenuation
2) Distance attenuation
dB
Distance attenuation value =
Refraction attenuation, sound path difference
δ
= A + B – d,
δ
=
3) Refraction attenuation
dB
Additional sound due to reflections (wall)
4) Additional sound from
reflections (wall surface)
dB
By calculation or the simplified method, the maximum value of the two
combined sounds is +3
Fig. 7, Addition sound due to reflection (ground surface)
5) Additional sound from
reflections (ground surface)
dB
By calculation or the simplified method, the maximum value of the two
combined sounds is +3
6)
Subtotals
dB
Conversion factors for A weighting
7) Overall A-weighting correction
factors
dB
-
26
-
16
-
9
-
3
0 +1 +1
-
1
8)
A
weighting
dB(A)
By completing the calculations in the above table, the overall A weighting at the reception point is obtained
(calculate in order from the highest sound level).
Once the overall A weighting has been calculated, combine with the ambient noise level to obtain to total sound
level at the reception point.
The overall A weighting at the reception point is
calculated to be 35.95 dB(A).
If the ambient noise (when the unit is not
operating) is 30.0 dB(A), the combining these
levels gives 36.9 dB(A).
Содержание ECO G SGP-EW120M2G2W
Страница 3: ...A 1 System Configuration Contents 1 Type Configuration 1 Outdoor unit A 2 ...
Страница 12: ...Outdoor Unit 3 External Dimensions B 8 ...
Страница 13: ...Outdoor Unit 4 Wiring Diagram B 9 ...
Страница 14: ...Outdoor Unit 5 Performance Characteristics B 10 Cooling Heating SGP EW120M2G2W ...
Страница 15: ...Outdoor Unit 5 Performance Characteristics B 11 Cooling Heating SGP EW150M2G2W ...
Страница 16: ...Outdoor Unit 5 Performance Characteristics B 12 Cooling Heating SGP EW190M2G2W ...
Страница 17: ...Outdoor Unit 5 Performance Characteristics B 13 Cooling Heating SGP EW240M2G2W ...
Страница 18: ...Outdoor Unit 6 Operating Sound Level Characteristics B 14 1 Standard Mode ...
Страница 19: ...Outdoor Unit 6 Operating Sound Level Characteristics B 15 ...
Страница 20: ...Outdoor Unit 6 Operating Sound Level Characteristics B 16 ...
Страница 21: ...Outdoor Unit 6 Operating Sound Level Characteristics B 17 ...
Страница 22: ...Outdoor Unit 6 Operating Sound Level Characteristics B 18 2 Quiet Mode ...
Страница 23: ...Outdoor Unit 6 Operating Sound Level Characteristics B 19 ...
Страница 24: ...Outdoor Unit 6 Operating Sound Level Characteristics B 20 ...
Страница 25: ...Outdoor Unit 6 Operating Sound Level Characteristics B 21 ...
Страница 28: ...Control Related 1 System Block Diagram C 2 ...
Страница 29: ...Control Related 2 Remote Control Warning List C 3 ...
Страница 30: ...Control Related 2 Remote Control Warning List C 4 ...
Страница 31: ...Control Related 2 Remote Control Warning List C 5 ...
Страница 38: ...System Design 3 Refrigerant piping design D 7 2 Selecting system header and branch piping sizes ...
Страница 75: ...Installation Work 1 Points regarding refrigerant pipe work E 2 1 Points regarding branch pipe work APR P160BG ...
Страница 76: ...Installation Work 1 Points regarding refrigerant pipe work E 3 APR P680BG ...
Страница 77: ...Installation Work 1 Points regarding refrigerant pipe work E 4 APR P1350BG ...
Страница 78: ...Installation Work 1 Points regarding refrigerant pipe work E 5 APR CHP680BG APR CHP1350BG ...
Страница 83: ...Installation Work 2 Points regarding electrical work outdoor unit E 10 1 Wiring thickness and device capacity ...
Страница 85: ...Installation Work 2 Points regarding electrical work outdoor unit E 12 3 Precautions regarding electrical work ...
Страница 86: ...Installation Work 2 Points regarding electrical work outdoor unit E 13 ...
Страница 87: ...Installation Work 3 Outdoor unit installation work E 14 ...
Страница 88: ...Installation Work 3 Outdoor unit installation work E 15 ...
Страница 89: ...Installation Work 3 Outdoor unit installation work E 16 ...
Страница 90: ...Installation Work 3 Outdoor unit installation work E 17 ...
Страница 91: ...Installation Work 3 Outdoor unit installation work E 18 ...
Страница 92: ...Installation Work 3 Outdoor unit installation work E 19 ...
Страница 93: ...Installation Work 3 Outdoor unit installation work E 20 ...
Страница 94: ...Installation Work 3 Outdoor unit installation work E 21 ...
Страница 95: ...Installation Work 3 Outdoor unit installation work E 22 ...
Страница 96: ...Installation Work 3 Outdoor unit installation work E 23 ...
Страница 97: ...Installation Work 3 Outdoor unit installation work E 24 ...
Страница 98: ...Installation Work 3 Outdoor unit installation work E 25 ...
Страница 99: ...Installation Work 3 Outdoor unit installation work E 26 ...
Страница 100: ...Installation Work 3 Outdoor unit installation work E 27 ...
Страница 101: ...Installation Work 3 Outdoor unit installation work E 28 ...
Страница 102: ...Installation Work 3 Outdoor unit installation work E 29 ...
Страница 103: ...Installation Work 3 Outdoor unit installation work E 30 ...
Страница 104: ...Installation Work 3 Outdoor unit installation work E 31 ...
Страница 105: ...Installation Work 3 Outdoor unit installation work E 32 ...
Страница 106: ...Installation Work 3 Outdoor unit installation work E 33 ...
Страница 107: ...F 1 Separately Sold Parts Contents 1 Outdoor unit related parts 1 Exhaust extension kit SGP PEX560K F 2 ...