2. Detailed Settings Function
W-2WAY ECO-i SYSTEM
Remote Controller Functions
Item code
Item
Setting data
No.
Description
Fan tap setting
(Fan tap change in order
to prevent drop in air
discharge caused by
filter installation)
DC fan tap operating
mode
Purpose
0000
Standard
Standard (setting at shipment)
0001
High ceiling use
High ceiling setting 1 (with standard panel)
For low
static-pressure filter
Ultra long-life filter, oil guard panel, ammonia deodorizing
filter, optical regenerative deodorizing filter
0003
High ceiling use
High ceiling setting 2 (with standard panel)
For low
static-pressure filter
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical regenerative
deodorizing filter, deodorant (activated charcoal) filter
For air-blocking
material
For 3-way discharge, when discharge duct is connected
0006
For air-blocking
material
For 2-way discharge
Humidifier ON time
(ON time per 60
seconds)
0000
No humidifier output
0001
1 sec.
0002
2 sec.
0058
58 sec.
0059
59 sec.
0060
Continuously ON
Repeat timer switching
0000
Function disabled
0001
Function enabled
Timer function change
prohibit
0000
Function disabled
0001
Function enabled
Smudging control
0000
No smudging control