5
5
- 10
4. W-2WAY ECO-i Alarm Codes
W-2WAY ECO-i SYSTEM
Trouble Diagnosis
E16 Alarm
Alarm code
E16
Alarm meaning
Automatic address setting alarm (too many units)
Alarm conditions
The number of indoor units was too many when automatic address setting was performed.
After initial communications were completed, an unrecognized unit was detected.
•
•
Probable cause
(1) The number of indoor units set at the indoor unit quantity setting SW (S004, S005) on the
outdoor unit PCB is less than the number set.
(2) The inter-unit control wiring is wired incorrectly.
Check
(1) Refer to the test run servicing materials and check the number of indoor units that is set.
(2) Check the inter-unit control wiring at the indoor and outdoor units.
Correction
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
Example
—
Notes
—
E20 Alarm
Alarm code
E20
Alarm meaning
No indoor units at automatic address setting.
Alarm conditions
When automatic address setting was performed, no indoor units were recognized.
Probable cause
(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
(2) Serial connector 1 (CN001) is disconnected at the outdoor unit.
(3) The power is OFF at all indoor units in the system.
Check
(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
(2) Check whether serial connector 1 (CN001) is disconnected at the outdoor unit.
(3) Check the power at the indoor units.
Correction
(1) Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.
Example
—
Notes
Position of serial connector CN001 on W-2WAY ECO-i
E24 Alarm
Alarm code
E24
Alarm meaning
Outdoor unit (INV) failed to receive communications from other outdoor unit (constant-speed).
Alarm conditions
After initial communications were completed, communications from an outdoor unit stopped.
Probable cause
(1) After initial communications were completed, the control wiring between main and sub
outdoor units was cut.
(2) After initial communications were completed, the outdoor unit power was turned OFF.
Check
—
Correction
—
Example
—
Notes
—
CN001