Item
Standard or Characteristics
Notes
Model
E11B102A001
E11B102A002
Output capacity
1 kVA / 0.8 kW
Cooling system
Forced air cooling
A
C
In
p
u
t
Input plug
NEMA 5-15P
IEC60320-C14
Inlet
IEC60320-C14
Number of phases
Single-phase 2-wire
Voltage
55 to 150 V
110 to 300 V
When in Double Conversion mode
Note 2
100 V, 110 V, 115 V, 120 V ±8% 200 V, 220 V, 230 V, 240 V, 208 V
±8%
When in Economy mode
Frequency
40 Hz to 120 Hz
Required capacity
1.1 kVA
Max. capacity during battery recovery charging
Power factor
0.95 or more
During rated output
Note 3
A
C
O
ut
p
ut
Outlet
NEMA 5-15R × 6
IEC60320-C13 × 6
Number of phases
Single phase 2-wire
Voltage
100 V, 110 V, 115 V, 120 V
200 V, 220 V, 230 V, 240 V,
208 V
Can be set by user
Note 4
Voltage regulation
Within rated voltage ±2%
When in Double Conversion mode
Frequency
50 Hz or 60 Hz
Same as the input frequency (auto-select)
Frequency accuracy
Within ±1% of the rated frequency
When the operation mode is set to
“Fixed to Double Conversion”
When UPS is
operating
(self-running):
Within ±0.5
Within ±1, 3, or 5% of the rated frequency
When the operation mode is set to
“Auto” Note 5
Voltage waveform
Sine wave
voltage harmonic
distortion
With a linear load: 3% or less
With a 100% rectifier load 8% or less
At rated output
T
ra
nsi
en
t V
o
lta
g
e
flu
ct
ua
tio
n
Rapid load
change
0 100% transient, at
rated input
During power
outage, recovery
Within ± 5% of the rated voltage
Note 6
At rated output
Input voltage
during rapid
change
For ±10% rapid voltage changes
Response time
5 cycles or less
Note 6
Load power factor
0.8 (lag)
Variation range 0.7 (lag) to 1.0
Overcurrent protection
Automatic transfer to bypass at 105% or more
With automatic retransfer function
Overload
capability
Inverter
105%
200 ms
Bypass
15 A (current protector)
8 A (current protector)
200% 30-second period / 800% 2 cycles (reference value)
B
a
tte
ry
Type
Small-sized valve-regulated lead-acid battery
Quantity
2
12 V / battery, serial
Rated capacity
68 W
15 minute rate
Backup time
3 min. (800 W)
5 min. (700 W)
At 25 C (77 F) ambient temperature, default setting Note 7
Heat dissipation
25 W
When in Economy mode
130 W
When in Double Conversion mode
Input leakage current
3 mA or less
Ambient conditions
Ambient temperature: -10 to +55 C (14 to 131 F)
Relative humidity: 20 to 90%
Note 8
Noise
40 db or less
When in Economy mode
1 m from front of UPS,
A-weighting,
45 db or less
When in Double Conversion mode
Note 1. The inverter is capable of operation synchronized with AC input frequency and switchover operation without interruption provided that the AC
input frequency is within the rated frequency range.
Note 2. A load reduction is required when the input voltage is within the range below.
UPS
Input Voltage Range
Load level
100 V Model
55 V to 68 V, 144 V to 150 V
Less than 40%
68 V to 80 V
Less than 70%
200 V Model
110 V to 136 V, 288 V to 300 V
Less than 40%
136 V to 160 V
Less than 70%
Note 3. When the distortion factor of the input voltage waveform is less than 1% in Double Conversion mode.
Note 4. Can be set by user. The default value is 100 V for a 100 V Model, and 200 V for a 200 V Model.
Note 5. Can be set by user. The default value is 3%.
Note 6. When in Double Conversion mode. The value depends on the utility power when in Economy mode.
Note 7. When the power management software or the LAN interface card is to be used, use the software or card in either of the following states.
• Set the time until UPS output stops (power outage verification time, shutdown delay time, UPS automatic shutdown time) to within 3 minutes
during a power outage.
• Use the software at a load level of 85% or less.
Note 8. The UPS contains batteries. The battery service life end will be foreshortened if the UPS is used in an environment where the ambient
temperature exceeds 30°C (86 F). When the ambient temperature exceeds 40 C (104 F), battery charging stops.
Note 9. If the unit is grounded, align the input/output grounding phase to the UPS specification.
Note 10. Some of the specifications for a UPS with long backup times differ from the specifications listed in the above table. See the extension battery
specifications instruction manual.
Note 11. The input voltage range that allows bypass operation is +20% or less of the output voltage setting. However, when “Bypass power supply
switch during input error” in the setting menu is set to “Disable”, the UPS cannot switch to bypass operation outside of the ranges - 30% or less
and 40 to 120 Hz.