6. INSPECTION AND MAINTENANCE
_
39
6
6
.
.
2
2
.
.
2
2
R
R
u
u
n
n
n
n
i
i
n
n
g
g
a
a
B
B
a
a
t
t
t
t
e
e
r
r
y
y
T
T
e
e
s
s
t
t
CAUTION
!
Perform a battery test periodically to check if the batteries have deteriorated. Using a deteriorated battery may result
in battery leakage and, in the worst case, smoke, a fire or a disaster. When the batteries have deteriorated, replace
them.
Run a battery test following the procedure below. If the UPS has performed a backup operation within 12 hours prior to the test, the
result may show an error. In such a case, conduct the test when the UPS has not performed a backup operation within the last 12
hours.
Step
Operation
UPS Status
1
Slide the cover of the control panel upward, and hold down
on the control panel for at least 2 seconds.
The [BATT.TEST (green)] blinks, and the battery test starts.
Buzzer sound: Beep-beep • • • •
•Beep-beep • • • • • •Beep-beep
[BATT.TEST (green)]: Blinking
The test is completed within a
period of approximately 1 minute.
2
Check the results of the battery test based on the lit state
of the [BATT.TEST (green)] and buzzer sound.
When the [BATT.TEST (green)] blinks and the buzzer
sounds, the batteries need to be replaced. Contact your
sales representative or SANYO DENKI.
Battery test result
Battery test result
OK
NG
3
After checking the displayed battery test results, press
.
[BATT.TEST (green)] on the display turns OFF, and the display
returns to normal.
[BATT.TEST (green)]: Lit
Buzzer sound: None
Hold down for at least
2 seconds
Replacing the batteries now is
recommended. Contact your sales
representative or SANYO DENKI.
The battery is normal.
[BATT.TEST (green)]: Blinking
Buzzer sound:
Beep-beep-beep-beep-beep-beep-beep
Continues (7 times)
Hold down for at
least 2 seconds