5. USING THE UPS (APPLICATION)
_
23
CAUTION
!
Use the UPS following the instructions in this instruction manual.
Improper use may result in an electric shock, bodily injury, and/or a fire.
Connect optional and external devices with the UPS input plug unplugged from the utility power outlet.
Failure to do so may result in electrical shock.
You can run the UPS in accordance with your system by configuring the various UPS functions and connecting optional devices.
For various optional device details, contact your sales representative or SANYO DENKI.
5
5
.
.
1
1
U
U
P
P
S
S
S
S
e
e
t
t
t
t
i
i
n
n
g
g
M
M
e
e
n
n
u
u
s
s
The UPS is provided with the setting menus described in the table below. Set the menus according to your environment,
system, and operation method.
For details on default setting, setting methods, and setting values, see the Setting Menu Manual.
For setting menu items marked with " ", after you change the value, the value will not take effect until after you restart
the UPS.
Setting Menu List
No.
Setting Menu
Default Setting
Description
1 UPS operation mode
*
1
Set the mode to UPS operation mode
2 Output voltage
*
1
Set the UPS output voltage. Same as the input voltage.
3 Synchronous frequency range
3%
Set the range (%) of the output frequency.
4 Interface
WS
Workstation
Set the interface for external interface connector use.
5 Baud rate
9600
Set the baud rate for connection with a workstation, personal computer, or
LAN interface card (option).
6 PC I/F connector
RS-232C
Set the PC I/F connector to be used.
7 UPS operation upon power recovery.
Automatic
Set the UPS operation to be performed when the utility power recovers after
the UPS stops due to end of battery discharge during a power outage.
8 Buzzer sound
All
Set when the buzzer should beep.
9 UPS OFF operation
1 sec
Set how to operate the
button when UPS is shut down.
10 Overload operation
Automatic return Set what to do after the power supply switches to bypass due to overload.
11 Operation during
OFF
OFF
Set the output power supply state when UPS stops.
12
Bypass power supply switch during
input error
Enable
Enable or disable power supply switches to bypass when an input error occurs.
13 Transmission signal at minor error
Output
Set whether or not to send a transmission signal when a minor error occurs.
14
Simulated transmission signal output
for device error
Do not output
Outputs a device error transmission signal for testing.
15
Simulated transmission signals for
battery voltage dip
Do not output
Outputs a low battery voltage transmission signal for testing.
16 Battery power startup
Disabled
Enables/Disables battery power startup when a utility power error occurs.
17 Timing of low battery voltage warning Battery voltage Set when to issue battery voltage low warning.
18 Battery test time
1 minute
Set the duration to perform battery test.
19 Backup time
*2
3 min.
Set the UPS backup time.
20 Battery type
*2
5 years
Set the battery type. Set during battery replacement or extension.
21 Battery test schedule
180 days
Set when (number of days) to run battery test automatically. The battery test is
implemented automatically when the set period elapses.
22 Recovery check time
0 sec.
Set the time until the UPS confirms that the utility power has recovered during
a power outage.
23 Remote switch input
Use ON/OFF Set the operation when the remote switch is connected.
24 Battery information Reset
*3
Do not reset
Reset / Do not reset remaining battery information
*1. The default value differs according to the UPS model number. See “Simplified Manual” supplied with the UPS.
*2. When the backup time and battery type settings are changed, the settings are not enabled unless the battery information is reset after the changes
are made.
*2. The battery life, accumulated battery operation time, power outage count, remaining LED life display, and elapsed battery test time are reset.
!
5
5
.
.
U
U
S
S
I
I
N
N
G
G
T
T
H
H
E
E
U
U
P
P
S
S
(
(
A
A
P
P
P
P
L
L
I
I
C
C
A
A
T
T
I
I
O
O
N
N
)
)
E
E
x
x
p
p
l
l
o
o
r
r
e
e
d
d
i
i
f
f
f
f
e
e
r
r
e
e
n
n
t
t
w
w
a
a
y
y
s
s
t
t
o
o
u
u
s
s
e
e
y
y
o
o
u
u
r
r
U
U
P
P
S
S
.
.