Maintenance
37
⑤
Pull the battery pack out.
⑥
Insert the new battery pack so that the connector faces forward.
⑦
Connect the battery connector.
⑧
Verify that Forced Bypass is set to “Inverter”.
⑨
Attach the battery cover.
⑩
Attach the front panel.
⑪
Set the backup time in the user setting. See §3.12 “Setting Battery Backup Time ”in the
User
Settings Guide
.
⑫
Set the battery type in the user setting. See § 3.13 “Setting Battery Type” in the
User Settings
Guide
.
⑬
Reset the battery information in the user setting. See §3.15 “ Resetting Battery Information” in the
User Settings Guide
.
⑧
Forced Bypass switch should be inverter
position.
⑥
Insert the new battery pack in
the direction of the arrow.
⑦
The connector cannot be inserted in
the wrong orientation. Check the
correct insert orientation, and push
in until you hear a click.
CAUTION
!
•
The battery connector cannot be inserted in the wrong orientation. If it does not go in,
do not try to force it. Doing so can damage the connector and result in electric shock.
•
Be careful not to get your hands caught when securing the cover.
This completes the battery exchange.
The batteries used in this product are lead type batteries which are a reusable resource. Please cooperate by
recycling when replacing or disposing of used batteries. Dispose of used batteries according to the instructions.
To dispose of used batteries, contact your nearest sales representative, an authorized industrial waste
handling company, or repack them in their original cartons and send them to your supplier. (An extra charge
is required.)
Note on the used battery
⑩
Place the front cover
over the battery cover,
and press it down.
⑨
Insert the tabs on the left and right
sides of the battery cover into the slots
and press it down until you hear a click
sound. Secure with the screws.