9
Instruction Manual for IL COIL CLEAN & ITS VARIOUS MODELS
1-888-726-8869
www.sanuvox.com
OPERATION
How to Operate your Product
The IL Coil Clean and its various models incorporate unique features into their ballast boxes. These include LED status display
as well as tow pairs of dry contacts designed to communicate with building automation systems.
CAUTION:
The suggested operating temperature range is 10 to 46°C (50 to 115°F). Operating the IL Coil Clean and its
various models outside this range will result in decreased performance.
How to Read the LED Status Display
Depending on the configuration and number of IL units ordered, there may be one or two ballast incorporated into the ballast
box. If there is only one ballast, you will notice only one wire set in the ballast box as well as a black cap covering the second
LED emplacement. If there is two (2) ballasts, there will be two wire set and two LED.
GREEN:
UV UNIT ON
The unit is functioning normally.
YELLOW:
UV LAMP NEEDS REPLACEMENT
Notifies the user that the UV lamp has reached the end of its lifespan and must be replaced.
FLASHING RED:
UV LAMP FAILURE
Lamp has failed or the unit is powered ON without any UV lamp installed.
LED OFF:
NO POWER
There is no power delivered to the unit or power supply is defective.
A reset button is located under the LED (when the cover is removed) allowing the user to reset the lamp timer back to zero after
the lamp replacement.
Dry Contacts for Building Automation Integration
Each IL Coil Clean and its various models includes a pair of dry contacts (NO and NC). Dry contacts make it possible for the IL
units to be easily tied to a building automation system.