5 / 32
Terminal block No.
Wiring to the external signal terminal block (screw-less)
While holding down the button on the terminal block with a flat-blade screwdriver or similar,
insert the wire into the wire insertion hole. Then, detach the flat-blade screwdriver to release
the button, and the wire will be fixed.
Applicable wire size
・
Terminal block (A), (S)
Stranded wire:
AWG26 - 20
Solid wire:
AWG26 - 20
Wire strip length: 10
–
11mm
・
Terminal block (B)
Stranded wire:
AWG22 - 14
Solid wire:
AWG22 - 14
Wire strip length: 9
–
10mm
Terminal block (A)
Signal name
Wire insertion hole
Lever
Board side connector for P4 cord
[Connected]
Terminal block (S)
Terminal block (B)
Output
Power