![Sanken NS-4A003-B Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/sanken/ns-4a003-b/ns-4a003-b_instruction-manual_809248052.webp)
PID
Function
F30xx
~
F33xx
-51-
PID
Function
F30xx
~
F33xx
Code
Function Name
Data Content
Setting
resolution
Factory
preset
3001
PID1 command value input
switching
1
:
Frequency
2
:
External analog VRF voltage
(
0
~
5V
)
3
:
External analog VRF voltage(0
~
10V
or potentiometer)
4
:
External analog V/I voltage
(
0
~
5V
)
5
:
External analog V/I voltage(0
~
10V
or potentiometer)
9
:
External analog V/I current
(
4
~
20mA
)
11
:
Function code setting
(
F3017
)
1
1
3002
PID1 Feedback input
switching
0: No input
1: External analog
VRF
voltage
(
0
~
5V
)
2:
External analog VRF voltage
(
0
~
10V
or potentiometer
)
3: External analog
V/I
voltage
(
0
~
5V
)
4:
External analog V/I voltage
(
0
~
10V
or potentiometer
)
8: External analog
V/I
current
(
4
~
20mA
)
10: Communication mode
1
0
3003
PID1 control proportion’
gain
0
~
100
0.01
0.1
3004
PID1 control integral
time
0.01
~
100
sec.
0.01
sec.
1
3005
PID1 control differential
time
0
~
100
sec.
0.01
sec.
0
3006
PID1control integral separation
judgement
value
5
~
100%
(
upper frequency limit reference
)
0.1%
100
3007
PID1 feedbak signal
Input filter time constant
1
~
500
(
set value
1=10ms
)
1
10
3008
Indirect
PID1
input
reference
5
~
100%
(
Target value reference
)
0.1%
20
3009
PID1 deviation limit
value
0
:
No limit
1
~
100%
(
Upper freuqncy limit reference
)
0.1%
100
3010
PID1 output limit value
0
:
No limit
1
~
100%
(
Upper frequency limit reference
)
0.1%
100