![Sanken NS-4A003-B Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/sanken/ns-4a003-b/ns-4a003-b_instruction-manual_809248041.webp)
-40-
Code
Function Name
Data Content
Setting
resolution
Factory
preset
1509
Selection of output
terminal
DO1
0
:
Unused
1
:
In operation 1
2
:
Undervoltage
3
:
End of simple scheduled operation
4
:
In operation 2
5
:
Frequency matching (1
st
speed frquency)
6
:
Frequency matching (1
st
~
16
th
speed frequency)
7
:
Frequency approach
8
:
Overload alarm level setting signal (the value of F1704 )
9: Electric thermistor pre-alarm signal(80% of electric
thermistor)
10
:
Radiator overheat pre-alarm signal
13
:
Excitiation and DC braking signals
14
:
Lower frequency limit matching signal
15
:
Upper frequency limit matching signal
18
:
FR signal 19
:
RR signal
20
:
2DF signal 21
:
3DF signal
22
:
5DF signal 23
:
9DF signal
24
:
AD2 signal 25
:
AD3 signal
26
:
JOG signal 27
:
MBS signal
28
:
ES signal 29
:
RST signal
32
:
Discharge resistor on signal
34
:
Frequency counter
(
output frequency
)
35
:
Frequency counter
(
command frequency
)
36
:
Overload alarm level setting signal (Including
Acceleration/Deceleration
)
43
:
Low speed detection signal
47
:
Motor speed counter
48
:
Forward run detection signal
49
:
Reverse run detection signal
60
:
breakdown output
61
:
In forward run
(
only for three wired
)
62
:
In reverse run
(
only for three wired
)
1
1
1512
Counter output
multiple
1
~
100
times
1 times
1