![Sanken NS-4A003-B Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/sanken/ns-4a003-b/ns-4a003-b_instruction-manual_809248033.webp)
-32-
Code
Function Name
Data Content
Setting
resolution
Factory
preset
1103
Starting frequency
0.05
~
60Hz
0.01Hz
1
1104
Operation start frequency
0
~
20Hz
0.01Hz
0
1105
Start delay time
0
~
5
sec.
0.1sec.
0
1106
Start standby time
0
~
120
sec.
0.1sec.
0
1107
Start standby frequency
0.05
~
60Hz
0.01Hz
5
1108
Restart after momentary
Power failure
0: Do not start
1: Restart
2: Compensation for momentary power failure
1
0
1109
Direction of rotation of
Motor
1
:
Forward and reverse run
2
:
Forward run only
3
:
Reverse run only
1
1
1110
Direction of rotation of
Motor (Setting through
Operation panel)
1
:
Forward
2
:
Reverse
1
1
1111
Braking method
1: Deceleration to stop
2: Deceleration to stop + DC braking
3: Free run stop
4: Deceleration to stop + continuously DC braking
1
1
1112
DC braking start frequency
0.05
~
20Hz
0.01Hz
0.5
1113
DC braking time
1
~
25
Sec.
0.1
Sec.
2
1114
DC braking force
1
~
10
1
5
1115
Duty cycle of brake resistor
0: No brake resistor
2
~
25%ED
98: No discharge resistor protection
(with discharge)
99: External brake unit
1%ED
※
1
1116
Discharge resistor on signal
Output time
0.01
~
10.00
sec.
0.01sec.
0.1
1117
Parameters setting
Continuously DC braking
0
:
Braking invalid
1
:
Braking Valid
2
:
Valid for braking time
1
1