SEC3002 FIRE ALARM CONTROL PANEL
Page 3 of 24
F.P.E. Out (+, -)
F.A. Out (+, -)
Output voltage
18.5
~
27.5VDC
Max. output current
0.5A
Fuse rating
F1AL250V
End of line resistor
4K7
Type of cable
Plain unscreened cable, 1.5mm
2
Cable diameter
1mm
2
~
2mm
2
Transmission distance
≤
1500m
Fault Out
(NC, COM, NO)
Contact capacity
30VDC@2A, [email protected]
Type of cable
Plain unscreened cable, 1.5mm
2
Cable diameter
1mm
2
~
2mm
2
24VK (+, -)
Output voltage
18.5 ~ 27.5VDC
Max. output current
0.6A
Fuse rating
F1AL250V
Type of cable
Plain unscreened cable, 1.5mm
2
Cable diameter
1mm
2
~
2mm
2
Input
Class change (+, -)
Input mode
Passive
Cable resistance
≤
500
Ω
Type of cable
Plain unscreened cable, 1.5mm
2
Cable diameter
1mm
2
~
2mm
2
Loop
Loop Out (+, -)
Loop In (+, -)
Output voltage
16.5
~
27.5VDC, pulse
Output current
0
~ 0.3
A
Loop type
Class A
Type of cable
Screened or unscreened twisted-pair, 1.5mm
2
Transmission distance
≤
1000m
Cable diameter
1mm
2
~
2mm
2
Network communication
RS-485
Max. number of FIPs
30
Transmission rate
9600 bps
Type of cable
Screened or unscreened twisted-pair, 1mm
2
Transmission distance
≤
1000m
Cable diameter
1mm
2
~
5mm
2
CAN
Max. number of panels
20
Transmission rate
Optional: 10K, 20K, 50K and 100K bps
Type of cable
Screened or unscreened twisted-pair, 1mm
2
Transmission distance
≤
1000m
Cable diameter
1mm
2
~
5mm
2
Physical dimensions
Approx. Dimensions of the panel (W
×
H
×
D)
430×560×170mm
Approx. weight (without battery)
12kg
Operating conditions
Temperature range: 0
°
C
~
45
°
C; Max relative humidity: 95% (40
°
C
±
2
°
C, no condensation)