SANJIANG SEC3002 Скачать руководство пользователя страница 12

SEC3002 FIRE ALARM CONTROL PANEL

Page 11 of 24

5.2 Functions available at access level 3

Press LOGIN button and input the six digital authorized password to get access to the
following menu options.

5.2.1 System setup
Besides some basic system setup of changing time/password, adjusting LCD brightness and
renaming the system as described at functions of access level 2 in the separate Operating
Manual, configuration about network, fire indicating panel and printer can be completed.

Network setup

Select the network setup option under the menu category of SYSTEM, the following window
(or similar) will appear.

The SEC3002’s network protocol allows the interconnection of 20 SEC3002 main panels by
CAN bus. To build a network, all panels should be registered on the central panel (Host No.1).
Tick the ‘Share’ option if alarm signal of the central panel is required to be transmitted to the
other sub panels. On the local sub panel, register the panels where its alarm signal is going to
be reported. Only the registered panels on a sub panel will receive and display alarm signals
from that panel.
In network, the time of the system is based on the time of the central panel, that is, when the
time of Host 1 is changed, time on other networking panels will be altered accordingly.

Note

: All panels in a network should be set with the same transmission rate. The number of each

panel should be different.

There are 4 transmission rates: 10K, 20K, 50K, 100K. Some factors like the total number of
network panels, the transmission distance of the system and the type of cable used should be
taken into consideration. Commonly, twisted-pair cable is used for a network of 2-5 panels
with the rate of 20K within 1000m.

Tips

: View the sending packets number and the receiving packets number on the bus through the

Check BUS quality

menu option under the DISABLE/TEST category to see if they are close to each

other, otherwise it means low ratio of success transmission where better to decrease the transmission
rate or improve the transmission medium. In addition, when a CRT is involved in, it is regarded as a
main panel and takes up a host number.

Caution

: The networking connection should be in series instead of a star or a ring way, otherwise

abnormal communication will present.

Содержание SEC3002

Страница 1: ......

Страница 2: ...l connections 7 4 Indications and Controls 8 4 1 LED indicators 8 4 2 Button controls 9 4 3 Zone indication and control panel 10 5 Commissioning and Programming 10 5 1 Overview 10 5 2 Functions availa...

Страница 3: ...essable fire detection panel with 1 loop of 324 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specification...

Страница 4: ...cable 1 5mm2 Cable diameter 1mm2 2mm2 Loop Loop Out Loop In Output voltage 16 5 27 5VDC pulse Output current 0 0 3A Loop type Class A Type of cable Screened or unscreened twisted pair 1 5mm2 Transmis...

Страница 5: ...rd In general the SEC3002 consists of 2 sections 1 The right internal section contains the main processor of A Board the I O communication interface of B Board the Buttons and LEDs Board the ZCP board...

Страница 6: ...Communication Board optional This board is optional for external communication with other panels or FIPs fire indicating panel Specifically up to 20 panels can be networked with each other through th...

Страница 7: ...NOT connect batteries before applying mains power first 3 5 Points connection to the loop The figure in next page shows a typical loop connection complete with detectors sounder strobes modules and l...

Страница 8: ...the wiring to be monitored If the circuit is unused the 4K7 resistor must still be connected A typical connection is shown below 2 Fault Out short for Fault Output The NO and COM are closed in normal...

Страница 9: ...refers to a 24V power supply It provides 24V output continuously and disconnects the power for about 2 seconds at the time the panel is reset 6 Class Change A programmable input By shorting this term...

Страница 10: ...disabled and flashes when it has a fault Disable has priority over fault F P E DISABLED Lit yellow to indicate the F P E Out is disabled 4 2 Button controls 0 9 Used to enter numbers letters and marks...

Страница 11: ...re is any fault with the zone it lights steadily when the zone is in disablement or test condition The control button then is used to activate sounders in that zone Note Each unit of LEDs with a butto...

Страница 12: ...panel will receive and display alarm signals from that panel In network the time of the system is based on the time of the central panel that is when the time of Host 1 is changed time on other netwo...

Страница 13: ...igned to Up to 30 FIPs can be included in this system The setting window is as below Printer setup The standard printer of PRINTER 02 compatible to the panel can be registered through the menu option...

Страница 14: ...e to the loop with a unique Address number The following is the setup for the Product Type of a detector Since the Product Type is an inherent attribute of a field device the optional product types pr...

Страница 15: ...e consider the detection zone as the same area of the alarm zone with the same zone number The Output Mode refers to the control mode of an output type module when transmitting signal to its following...

Страница 16: ...setup the Causes apply to all devices in the system Press Add to create a rule and press Del to delete one To enable a c e press the Reg The default value of Num of fire signal is 01 which means once...

Страница 17: ...ers Additionally for convenience of customized function the button s utility can be defined additionally The setup window is shown below It is always recommended that the default settings be registere...

Страница 18: ...ble point in real time When selected you will be prompted to enter the specific address of the device you want to put into test Enter the target point and press OK to start the point test Module start...

Страница 19: ...o the detector module setup window with the Reg and Product Type data overwritten by the new auto learned data which means the previous system configuration will be changed So take care about this bef...

Страница 20: ...follow its tips Update system The system allows to be updated on site with additional functions by using a U disk at the authorized engineer level for future development Copy the file needed to the U...

Страница 21: ...IP In which The multiplier 1 25 is present to account for loss of capacity over the life of the battery IFq 0 3A which is the quiescent current of the fire alarm control panel in the event of the los...

Страница 22: ...er to the panel but the LCD display is off and panel does not work Possible reason and solution check if the fuse on the PSE Filter blows out Check if the POWER indicator on the front panel is on othe...

Страница 23: ...use is slipped over the pins accordingly Problem no indication is given by the ZCP when there is a zonal fire zonal fault etc Possible reason and solution the setup for ZCP is not registered The ZCP c...

Страница 24: ...Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventional Ionizat...

Страница 25: ...Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emergency Lightn...

Страница 26: ......

Отзывы: