SEC3002 FIRE ALARM CONTROL PANEL

Page 13 of 24

Zone setup

When this menu option is selected, a window is shown to allow you to register and add a
description for a specific zone, and to configure the ‘Resound’ option.

Note

: When using the panel networking function, in order to avoid displaying confusion or

communication error, try to configure and register different zones on different networking panels.

Detector/module setup

All detectors and modules in the system can be configured under this setup window by
completing the corresponding options.

Tick the ‘Reg’ will register and assign the device to the loop with a unique ‘Address’ number.
The following is the setup for the Product Type of a detector:

Since the Product Type is an inherent attribute of a field device, the optional product types
provided in this system are listed as follows.

Ionization detector

Optical detector

Heat detector

Strobe

Infrared detector

Combination detector JS input module

Gas detector

JK input module

Output module

Input/output module I/O module-Broadcast

KZJ_LD module

Manual control button Manual call point

Fire indicating panel

Fire hydrant call point

Sounder strobe

Sounder

The following figure shows the setup for the Device Type of an output module:

The ‘Resound’ function is selected
to determine whether the silenced
sounder(s) of all zones will be
resounded on a new fire signal
from any other zone.

Содержание SEC3002

Страница 1: ......

Страница 2: ...l connections 7 4 Indications and Controls 8 4 1 LED indicators 8 4 2 Button controls 9 4 3 Zone indication and control panel 10 5 Commissioning and Programming 10 5 1 Overview 10 5 2 Functions availa...

Страница 3: ...essable fire detection panel with 1 loop of 324 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specification...

Страница 4: ...cable 1 5mm2 Cable diameter 1mm2 2mm2 Loop Loop Out Loop In Output voltage 16 5 27 5VDC pulse Output current 0 0 3A Loop type Class A Type of cable Screened or unscreened twisted pair 1 5mm2 Transmis...

Страница 5: ...rd In general the SEC3002 consists of 2 sections 1 The right internal section contains the main processor of A Board the I O communication interface of B Board the Buttons and LEDs Board the ZCP board...

Страница 6: ...Communication Board optional This board is optional for external communication with other panels or FIPs fire indicating panel Specifically up to 20 panels can be networked with each other through th...

Страница 7: ...NOT connect batteries before applying mains power first 3 5 Points connection to the loop The figure in next page shows a typical loop connection complete with detectors sounder strobes modules and l...

Страница 8: ...the wiring to be monitored If the circuit is unused the 4K7 resistor must still be connected A typical connection is shown below 2 Fault Out short for Fault Output The NO and COM are closed in normal...

Страница 9: ...refers to a 24V power supply It provides 24V output continuously and disconnects the power for about 2 seconds at the time the panel is reset 6 Class Change A programmable input By shorting this term...

Страница 10: ...disabled and flashes when it has a fault Disable has priority over fault F P E DISABLED Lit yellow to indicate the F P E Out is disabled 4 2 Button controls 0 9 Used to enter numbers letters and marks...

Страница 11: ...re is any fault with the zone it lights steadily when the zone is in disablement or test condition The control button then is used to activate sounders in that zone Note Each unit of LEDs with a butto...

Страница 12: ...panel will receive and display alarm signals from that panel In network the time of the system is based on the time of the central panel that is when the time of Host 1 is changed time on other netwo...

Страница 13: ...igned to Up to 30 FIPs can be included in this system The setting window is as below Printer setup The standard printer of PRINTER 02 compatible to the panel can be registered through the menu option...

Страница 14: ...e to the loop with a unique Address number The following is the setup for the Product Type of a detector Since the Product Type is an inherent attribute of a field device the optional product types pr...

Страница 15: ...e consider the detection zone as the same area of the alarm zone with the same zone number The Output Mode refers to the control mode of an output type module when transmitting signal to its following...

Страница 16: ...setup the Causes apply to all devices in the system Press Add to create a rule and press Del to delete one To enable a c e press the Reg The default value of Num of fire signal is 01 which means once...

Страница 17: ...ers Additionally for convenience of customized function the button s utility can be defined additionally The setup window is shown below It is always recommended that the default settings be registere...

Страница 18: ...ble point in real time When selected you will be prompted to enter the specific address of the device you want to put into test Enter the target point and press OK to start the point test Module start...

Страница 19: ...o the detector module setup window with the Reg and Product Type data overwritten by the new auto learned data which means the previous system configuration will be changed So take care about this bef...

Страница 20: ...follow its tips Update system The system allows to be updated on site with additional functions by using a U disk at the authorized engineer level for future development Copy the file needed to the U...

Страница 21: ...IP In which The multiplier 1 25 is present to account for loss of capacity over the life of the battery IFq 0 3A which is the quiescent current of the fire alarm control panel in the event of the los...

Страница 22: ...er to the panel but the LCD display is off and panel does not work Possible reason and solution check if the fuse on the PSE Filter blows out Check if the POWER indicator on the front panel is on othe...

Страница 23: ...use is slipped over the pins accordingly Problem no indication is given by the ZCP when there is a zonal fire zonal fault etc Possible reason and solution the setup for ZCP is not registered The ZCP c...

Страница 24: ...Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventional Ionizat...