SEC3002 FIRE ALARM CONTROL PANEL

Page 18 of 24

5.2.5 Advanced functions
Besides some essential system configurations mentioned above, this ADVANCE category
provides supplementary functions for system commissioning including loop learn, data
load/backup, file reset and update of the system.

Loop learn

This function activates the panel’s automatic loop learn facility. As it prompts below, the loop
learn process may take about 120s and it cannot be stopped during the period.

When the auto-learn completes successfully, a comparison between the loop learn result and
the initial data will be given. And as it prompts, selecting Confirm will get entry to the
detector/module setup window with the Reg and Product Type data overwritten by the new
auto-learned data, which means the previous system configuration will be changed. So take
care about this before you continue with it. See the picture below.
Additionally, other attributes about the device will be set as default settings, for example, the
devices will be all assigned to zone 1 which can be modified as designed later.
When the time counted is over, the loop learn fails and it prompts timeout error.

Save data to U-disk

This function will copy the file of system configuration to the U-disk you insert at the top right
USB port of the front panel.

Note

: Choose a U-disk of capacity within 32G and make sure its file system is FAT32 or FAT16,

otherwise format it on computer. The remaining capacity of the U-disk should be above 2M for data
backup

.

Содержание SEC3002

Страница 1: ......

Страница 2: ...l connections 7 4 Indications and Controls 8 4 1 LED indicators 8 4 2 Button controls 9 4 3 Zone indication and control panel 10 5 Commissioning and Programming 10 5 1 Overview 10 5 2 Functions availa...

Страница 3: ...essable fire detection panel with 1 loop of 324 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specification...

Страница 4: ...cable 1 5mm2 Cable diameter 1mm2 2mm2 Loop Loop Out Loop In Output voltage 16 5 27 5VDC pulse Output current 0 0 3A Loop type Class A Type of cable Screened or unscreened twisted pair 1 5mm2 Transmis...

Страница 5: ...rd In general the SEC3002 consists of 2 sections 1 The right internal section contains the main processor of A Board the I O communication interface of B Board the Buttons and LEDs Board the ZCP board...

Страница 6: ...Communication Board optional This board is optional for external communication with other panels or FIPs fire indicating panel Specifically up to 20 panels can be networked with each other through th...

Страница 7: ...NOT connect batteries before applying mains power first 3 5 Points connection to the loop The figure in next page shows a typical loop connection complete with detectors sounder strobes modules and l...

Страница 8: ...the wiring to be monitored If the circuit is unused the 4K7 resistor must still be connected A typical connection is shown below 2 Fault Out short for Fault Output The NO and COM are closed in normal...

Страница 9: ...refers to a 24V power supply It provides 24V output continuously and disconnects the power for about 2 seconds at the time the panel is reset 6 Class Change A programmable input By shorting this term...

Страница 10: ...disabled and flashes when it has a fault Disable has priority over fault F P E DISABLED Lit yellow to indicate the F P E Out is disabled 4 2 Button controls 0 9 Used to enter numbers letters and marks...

Страница 11: ...re is any fault with the zone it lights steadily when the zone is in disablement or test condition The control button then is used to activate sounders in that zone Note Each unit of LEDs with a butto...

Страница 12: ...panel will receive and display alarm signals from that panel In network the time of the system is based on the time of the central panel that is when the time of Host 1 is changed time on other netwo...

Страница 13: ...igned to Up to 30 FIPs can be included in this system The setting window is as below Printer setup The standard printer of PRINTER 02 compatible to the panel can be registered through the menu option...

Страница 14: ...e to the loop with a unique Address number The following is the setup for the Product Type of a detector Since the Product Type is an inherent attribute of a field device the optional product types pr...

Страница 15: ...e consider the detection zone as the same area of the alarm zone with the same zone number The Output Mode refers to the control mode of an output type module when transmitting signal to its following...

Страница 16: ...setup the Causes apply to all devices in the system Press Add to create a rule and press Del to delete one To enable a c e press the Reg The default value of Num of fire signal is 01 which means once...

Страница 17: ...ers Additionally for convenience of customized function the button s utility can be defined additionally The setup window is shown below It is always recommended that the default settings be registere...

Страница 18: ...ble point in real time When selected you will be prompted to enter the specific address of the device you want to put into test Enter the target point and press OK to start the point test Module start...

Страница 19: ...o the detector module setup window with the Reg and Product Type data overwritten by the new auto learned data which means the previous system configuration will be changed So take care about this bef...

Страница 20: ...follow its tips Update system The system allows to be updated on site with additional functions by using a U disk at the authorized engineer level for future development Copy the file needed to the U...

Страница 21: ...IP In which The multiplier 1 25 is present to account for loss of capacity over the life of the battery IFq 0 3A which is the quiescent current of the fire alarm control panel in the event of the los...

Страница 22: ...er to the panel but the LCD display is off and panel does not work Possible reason and solution check if the fuse on the PSE Filter blows out Check if the POWER indicator on the front panel is on othe...

Страница 23: ...use is slipped over the pins accordingly Problem no indication is given by the ZCP when there is a zonal fire zonal fault etc Possible reason and solution the setup for ZCP is not registered The ZCP c...

Страница 24: ...Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventional Ionizat...

Страница 25: ...Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emergency Lightn...

Страница 26: ......

Отзывы: