SEC3002 FIRE ALARM CONTROL PANEL
Page 16 of 24
Zonal c&e
In this section, the Causes apply to devices in the given zone. The c&e meaning of the figure
below is when any one of smoke detector, heat detector or manual call point is active in zone
2, the fire pump wired after the I/O module with the address of 153 will be triggered after 5s.
Specific c&e
In this section, the Causes can apply to specific devices by entering their assigned addresses.
Maximum of 5 points can be set at one time. Here the meaning of its c&e rule is only when all
the points set in the conditions are active, the outputs could take place.
ZCP setup
On the zone indication and control panel (ZCP), each of the 32 buttons is used to activate the
loop sounders of a unique zone under default settings, i.e. at the authorized level of access
level 2 or 3, pressing a button on ZCP will activate the matched zonal sounders. Additionally,
for convenience of customized function, the button’s utility can be defined additionally. The
setup window is shown below.
It is always recommended that the default settings be registered, except a start/stop control
of a specified device with a button is specially expected, then tick the ‘Field device’ option and
choose from the Module List a device that you want to match. Remember to change a label
denoting it after configuration. Usually when the total number of zones configured is less than
32, you take advantage of this function. For example, the system is configured only to 20
zones, you may assign the other 12 units for controls and indications of some specific devices.
There are 32 default configurations for
each unit of LEDs with a button.
Similar to the left, register the default
setting so that each unit corresponds
to a unique zone as it defines.
The meaning of this c&e is when any 2 of
smoke detector, heat detector or manual
call point are active, the electromagnetic
valve wired after the I/O module with the
address of 155 will be triggered after 10s.