28
Parameter
Value
Max. allowed temperature.
40°C
Permitted fluid
up to 70°C for max.
5 minutes per hour
Max. room temperature.
50°C
Operating mode
Intermittent service
SANIFOS
®
110 P, and 280: S3 30 %
Intermittent service
SANIFOS
®
610 and SANIFOS
®
1300: S3 50%
SANIFOS
®
610 and SANIFOS
®
1300 Vortex
three-phase : S3 30%
7.3 Starting and stopping
The automatic control starts and stops the pump when a defined level is reached.
The position of each float is set at the factory.
Never change this setting.
In the event of replacement of one or more float switches for maintenance operations, position them as shown in the
illustration opposite.
The free length of the floats shall be 150 mm ± 5 from the point of attachment of the cable to the base of the float.
Ensure that the floats move freely.
7.4 Starting frequency
To prevent engine overheating and excessive stress on the engine, seals and bearings, limit the number of starts to 10
per hour.
7.5 Commissioning with the control box
7.6 Operations required for commissioning
1.
Perform a functional and sealing test of the pumping station: once the hydraulic and electrical connections are made,
check the connections for leaks by running water successively through each inlet used. Ensure the device is operating
properly and there are no leaks by performing a water test and observing several start cycles.
2.
Check the various points on the checklist (section 9.1, page
30).
3.
WARNING: Do not run the engine in forced mode (by pressing the key on the keypad) before putting the pump in
water. Dry running damages the grinding system.
SANIFOS
®
610 floats
The control box cover is not properly closed. Risk of electric shock!
➜
Properly close the control box cover.
➜
Then reconnect the power plug.
SANIFOS
®
1300 floats
Содержание SANIFOS 110 P