27
VSD settings for 50 Hz
MYMn
Parameter
Nom volt
UnS
230 V/400 V
Nom amps
nCr
Dep on motor
Output freq
FrS
50 Hz
Nom speed
nSP
Dep on motor
Ctrl type
Ctt
U/Fq
Base freq
bFr
50 Hz
Int therm prot
ItH
Dep on motor
MIN speed
LSP
15 Hz
MAX speed
HSP
50 Hz
PID min output
POL
15 Hz
PID max output
POH
50 Hz
Intern ref PID
PII
Si
Intern ref PID
rPI *
50
Prop gain PID
rPG
1
Intern gain PID
rIG
1
Comand Bloq func
FbCd
Start/Stop
Last error regist
M008
VSD settings for 60 Hz
MYMn
Parameter
Nom volt
UnS
230 V/400 V
Nom amps
nCr
Dep on motor
Output freq
FrS *
60 Hz
Nom speed
nSP
Dep on motor
Ctrl type
Ctt
U/Fq
Base freq
bFr *
60 Hz
Int therm prot
ItH *
Dep on motor
MIN speed
LSP *
18 Hz
MAX speed
HSP *
60 Hz
PID min output
POL *
18 Hz
PID max output
POH *
60 Hz
Intern ref PID
PII
Si
Intern ref PID
rPI *
50
Prop gain PID
rPG *
1
Intern gain PID
rIG *
1
Comand Bloq func
FbCd *
Start/Stop
Last error regist
M008
5.4. VSD ERROR SUMMARY TABLE
M008 is a read only parameter, and is the reference of the last error registered by the VSD.
At the informative level it is important to review this parameter in case of FAULT.
Below is a list of possible error codes.
LFT
0 [No fault] (nOF)
2 [Control Eeprom] (EEF1)
3 [Incorrect config.] (CFF)
4 [Invalid config.] (CFI)
5 [Modbus com.] (SLF1)
6 [int. com.link] (ILF)
7 [Com. network] (CnF)
8 [External flt-LI/Bit] (EPF1)
9 [Overcurrent] (OCF)
10 [Precharge] (CrF)
11 [Speed fdback loss] (SPF)
12 [Load slipping] (AnF)
16 [Drive overheat] (OHF)
17 [Motor overload] (OLF)
18 [Overbraking] (ObF)
19 [Mains overvoltage] (OSF)
20 [1 output phase loss] (OPF1)
21 [Input phase loss] (PHF)
22 [Undervoltage] (USF)
23 [Motor short circuit] (SCF1)
24 [Overspeed] (SOF)
25 [Auto-tuning] (tnF)
26 [Rating error] (InF1)
27 [PWR Calib.] (InF2)
28 [Int.serial link] (InF3)
29 [Int.Mfg area] (InF4)
30 [Power Eeprom] (EEF2)
32 [Ground short circuit] (SCF3)
33 [3out ph loss] (OPF2)
34 [CAN com.] (COF)
35 [Brake control] (bLF)
38 [External fault com.] (EPF2)
41 [Brake feedback] (brF)
42 [PC com.] (SLF2)
44 [Torque/current lim] (SSF)
45 [HMI com.] (SLF3)
49 [LI6=PTC probe] (PtFL)
50 [PTC fault] (OtFL)
51 [Internal- I measure] (InF9)
52 [Internal-mains circuit] (InFA)
53 [Internal- th. sensor] (InFb)
54 [IGBT overheat] (tJF)
55 [IGBT short circuit] (SCF4)
56 [Motor short circuit] (SCF5)
58 [Out. contact. stuck] (FCF1)
59 [Out. contact. open.] (FCF2)
64 [input contactor] (LCF)
67 [IGBT desaturation] (HdF)
68 [Internal-option] (InF6)
69 [internal- CPU] (InFE)
71 [AI3 4-20mA loss] (LFF3)
73 [Cards pairing] (HCF)
76 [Load fault] (dLF)
77 [Bad conf] (CFI2)
99 [Ch.sw. fault] (CSF)
100 [Pr.Underload.Flt] (ULF)
101 [Proc.Overload Flt] (OLC)
105 [Angle error] (ASF)
107 [Safety fault] (SAFF)
108 [FB fault] (FbE)
109 [FB stop flt.] (FbES)
In the event of a VSD fault, please contact S&P after-sales service, indicating the error that is displayed.