During maintenance, it is necessary to check the tightening of the terminals, clean the space of the heater terminal block from dust and dirt, 
monitor whether some components show signs of excessive warming, water leakage, mechanical or other damage. Increased attention must be 
paid to safety circuits, especially the thermal protection of the heater, including the correct response of the control system or power supply 
switchboard. Faults found must be rectified immediately. These inspections are carried out at least once a year (or more often according to local 
conditions) by an authorized professional service company.

 

Example of connection of the two section electric heater terminal block:

 

SAFETY THERMOSTAT 
AUTOMATIC RESET 

EMERGENCY THERMOSTAT 
MANUAL RESET 

Connection terminal block is accessible after removal of the heater front cover.

 

5.2.4 WATER HEATER CONNECTION

 

The unit fitted with the water heater (unit code DCA or DCB) is connected to the heating media by means of three-way mixing unit (see

 

"Types of ESU control units"). The water heater outlets are located on the front of the unit and are threaded. The exchanger must be connected 
in counter-current to the flow of air passing through (in concurrent connection, the exchanger loses approx. 25% of its output). When tightening 
the heat exchanger connections, it is necessary, for example, to hold the heat exchanger neck with a second wrench so that the tightening 
torque is not transmitted to the heat exchanger body.

 

Table of dimensions of water cooler connection necks:

 

www.solerpalau.co.uk

 

Size unit

 

heater/cooler type

 

thread

 

6000

 

6900

 

7800

 

IBW-A DUOVENT

®

 6000 DC (80/60)

 

G1.1/4"

 

IBW-B DUOVENT

®

 6000 DC (45/35)

 

IBW-A DUOVENT

®

 6900 DC (80/60)

 

G1.1/4"

 

G1.1/4"

 

IBW-B DUOVENT

®

 6900 DC (45/35)

 

IBW-A DUOVENT

®

 7800 DC (80/60)

 

G1.1/4"

 

G1.1/4"

 

IBW-B DUOVENT

®

 7800 DC (45/35)

 

G1.1/4"

 

Size unit

 

heater/cooler type

 

thread

 

500

 

800

 

1200

 

1800

 

3000

 

4200

 

5100

 

IBW-A DUOVENT

®

 500 DC (80/60)

 

G1/2"

 

IBW-B DUOVENT

®

 500 DC (45/35)

 

IBW-A DUOVENT

®

 800 DC (80/60)

 

G1/2"

 

G1/2"

 

IBW-B DUOVENT

®

 800 DC (45/35)

 

IBW-A DUOVENT

®

 1200 DC (80/60)

 

G1/2"

 

G1/2"

 

IBW-B DUOVENT

®

 1200 DC (45/35)

 

IBW-A DUOVENT

®

 1800 DC (80/60)

 

G1/2"

 

G3/4"

 

IBW-B DUOVENT

®

 1800 DC (45/35)

 

IBW-A DUOVENT

®

 3000 DC (80/60)

 

G3/4"

 

G1"

 

IBW-B DUOVENT

®

 3000 DC (45/35)

 

IBW-A DUOVENT

®

 4200 DC (80/60)

 

G1"

 

G1.1/4"

 

IBW-B DUOVENT

®

 4200 DC (45/35)

 

IBW-A DUOVENT

®

 5100 DC (80/60)

 

G1.1/4"

 

G1.1/4"

 

IBW-B DUOVENT

®

 5100 DC (45/35)

 

G1.1/4"

 

CAUTION!

 

before service works!

 

• The unit must be disconnected from the power supply

 

•  The fan impellers shall not rotate

 

•  Electric heater bars must be cooled to min. 30 °C

 

•  The unit service switch is locked in OFF position

 

CAUTION!

 

It is forbidden to remove, bypass or disconnect safety devices, safety 
functions and protective devices! Any intervention in the internal

 

connection of the heater is forbidden!

 

Ventilation unit with heat recovery

DUOVENT

®

 COMPACT DV

 

Содержание DUOVENT COMPACT DV

Страница 1: ...INSTRUCTION MANUAL www solerpalau co uk DUOVENT COMPACT DV Ventilation unit with heat recovery...

Страница 2: ...n Connection of electric heater Connection of water heater Connection of water cooler Connection of direct evaporator Connection of condensate drain Bypass and mixing flap Inlet and outlet flap 5 2 10...

Страница 3: ...ation Warranty conditions The device must be installed by a professional air handling service company DUOVENT COMPACTDV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by t...

Страница 4: ...hat could affect safety and proper function are prohibited Installation and operating documentation must be available to the operator and service It is advisable to place it close to the installed uni...

Страница 5: ...nit for ventilation of pool halls Order examples DUOVENT COMPACT DV 3000 DI DX MX KL G4 F7 F7 DVAV JH2 Unit size 3000 with electric heater direct evaporator bypass and mixing flap two stage filtration...

Страница 6: ...INSULATION OF THE ANTIFREEZE PROTECTION CONTACT SENSOR WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNI...

Страница 7: ...0 182 DUOVENT DV 1200 521 992 312 80 2091 260 5 260 5 582 300 500 DUOVENT COMPACT DV 500 to 1200 under ceiling arrangement positions xH AH unit position drawn UNIT BOTTOM VIEW Exchanger outlets UNIT T...

Страница 8: ...2 X3 L Y D Y Exchanger outlets D 20 D 1 2 1 2 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 19 18 18 18 Condensate drains 152 152 152 21 www solerpalau co uk 40 A 150 B A B 150 F 157 42 42 X1 X...

Страница 9: ...94 694 694 627 627 694 694 694 694 694 1085 1085 1085 1085 1085 1085 1085 DUOVENT COMPACT DV 1800 to 7800 floor arrangement positions xP AP unit position drawn X3 X1 X2 X E E X 1 2 1 2 19 18 18 18 Tra...

Страница 10: ...00V 50Hz 3000 1238 927 1 8 1 4 89 1 3500 320 387 3000 DCA DCC 3000 DCA DX 21 8 21 8 21 3 21 3000 DI 15 22 4200 4200 DCA 4200 DCB 4200 DCA DCC 4200 DCA DX 4200 DI 29 8 22 30 2 20 5 29 8 3 400V 50Hz 420...

Страница 11: ...ES EXCHANGER OUTLETS ETC Ensure proper balancing of the transported unit The ropes above the unit must be stretched to prevent damage The outdoor variants of the units are fitted with transport profil...

Страница 12: ...is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate formed in the air duct can in unfavourable conditions spill into the interior of the unit where...

Страница 13: ...tion box 5 1 2 HOW TO STORE THE UNIT AT THE DESTINATION The unit is designed for floor mounting in a vertical position positions marked xV in the unit code or horizontal position positions marked xP i...

Страница 14: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with...

Страница 15: ...let and outlet ports with respect to the position of the exchanger connection pipes Neck variants vertical arrangement viewed from unit operation side INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INL...

Страница 16: ...TLET OUTLET www solerpalau co uk INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET...

Страница 17: ...INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET...

Страница 18: ...n it is exceeded the operating thermostat opens and switches off the heater after cooling below 60 C the heater automatically switches on again Location of the release button under the cover on the un...

Страница 19: ...nger connections it is necessary for example to hold the heat exchanger neck with a second wrench so that the tightening torque is not transmitted to the heat exchanger body Table of dimensions of wat...

Страница 20: ...n screws on the heat exchanger collectors The heat exchanger can then be disconnected from the heating water distribution system and removed from the unit Max operating water temperature of water heat...

Страница 21: ...the cooler must be vented after connecting and filling the system with cooling water The vent screws are located directly at the heat exchanger connection necks The vent screws are accessible either...

Страница 22: ...specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a technician with the appropriate authorization according to the law 5 2...

Страница 23: ...ING FLAP In the basic version each unit is equipped with a bypass flap of the plate heat exchanger BP The bypass is used for summer ventilation defrost control of the recuperation exchanger in the eve...

Страница 24: ...on mode Location of mixing and bypass flap for DUOVENT 500 800 1200 units with MX mixing mode www solerpalau co uk ETA flap Mixing flap MX ODA flap Bypass flap BP Circulation flap C part 1 ODA flap Ci...

Страница 25: ...uators 5 2 10 BASIC ACCESSORIES 5 2 10 1 CONDENSATE DRAIN TRAPS Condensate traps must be ordered as a separate item as they are not included with the unit Vacuum type siphon scheme SF P 300 bottom edg...

Страница 26: ...ected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When placed under the ceiling it is necessary to maintain control an...

Страница 27: ...I C control system to the electrical distribution network is made by a separate supply cable which is not part of the delivery of the device www solerpalau co uk Ventilation unit with heat recovery DU...

Страница 28: ...ts according to the set parameters in the automatic summer winter mode according to the outdoor temperature and time dependencies Manual mode selection is also possible The heater can be hot water con...

Страница 29: ...otation of the fans the correct phasing of the damper actuators and mixing valves If the unit is equipped with a Digireg control system directly from the factory a SETPACK test package has been perfor...

Страница 30: ...onnection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATION The material content of the comprehe...

Страница 31: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with t...

Страница 32: ...NH IH2 JH2 MH2 NH2 263 295 263 365 KH LH OH PH KH2 LH2 OH2 PH2 263 295 263 295 1200 1200 all positions 420 365 365 420 ETA filter size ETA mm ODA filter size ETA mm Size of DUOVENT DV Vnom m3 h Neck...

Страница 33: ...replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove the fan as shown in the following figure K...

Страница 34: ...nitor the implementation of the measures taken Check the siphons for condensate drainage especially their permeability and tightness especially the tightness of the mounting on the unit and the tightn...

Страница 35: ...l applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be a...

Отзывы: