6.3 INSTRUMENTATION AND CONTROL (I&C) SYSTEM

 

The standard part of the unit is its own control system. The design of the unit is ready for cooperation with the Digireg

®

 digital controller.

 

6.3.1 

DIGITAL REGULATION SYSTEM DIGIREG

®

 

The control system is located in a compact sheet steel switchboard equipped with a main switch, digital controller on the PCB board and safety 
and switching elements for individual HVAC units. The cables pass through plastic bushings with locking in the left side of the cabinet.

 

Basic dimensions of Digireg

®

 M3-Vx switchboard with protection level IP20: 

The switchboards M1-E2 to M3-E36 have dimensions 660 x 660 x 120 mm.

 

The Digireg

®

 switchboard with IP65 protection has dimensions of 640 x 600 x 210 mm.

 

6.3.2 TEMPERATURE REGULATION

 

The Digireg

®

 controller is designed to control the output of the heater or cooler of the air handling unit to reach the desired temperature. Digireg

®

 

can command direct cooling or a  heat  pump. There is  a 3-point output for servo drive of the mixing valve, direct power outputs SSR for electric 
heating or two analogue outputs 0

–10 V / 0–20 mA. The heat pump or cooling unit is controlled by potential-free contacts.

 

Regulation to a constant supply air temperature

uses one temperature sensor in the supply pipe, the supply air is heated or cooled to the required set temperature within the minimum and
maximum configured temperature

Regulation to a constant temperature of the exhaust air

uses one temperature sensor in the exhaust pipe, the supplied air is heated or cooled to the required set temperature within the minimum
and maximum configured temperature

Spatial temperature control (for constant room temperature)

cascade control is used with limitation of the minimum and maximum supply air temperature. The main sensor is placed in a ventilated
area, the supply air sensor is placed in the outlet of the unit in a place with sufficient air mixing. If the room temperature is higher than the
set value, the controller will try to reduce the supply air temperature to the set minimum supply air temperature. If the room temperature
falls below the set value, the controller tries to compensate for this by increasing the supply air temperature. The room temperature can be
selected as the room temperature, the temperature from the sensor in the controller, or from a separate sensor connected
to the motherboard. The controller cools or heats according to the set parameters in the automatic summer/winter mode according to the
outdoor temperature 

and time dependencies. 

Manual mode selection is also possible. The heater can be hot water, controlled by a three-

point actuator, or electric, directly controlled by SSR, or external TRIAC switches 0-10 V. Electric heater controlled by internal SSR can
have up to 36 kW depending on the cabinet, water heater is not limited mixing unit size). Cooling can be cold water, controlled by a 0-10 V
analogue actuator or direct in conjunction with a condensing cooling unit.

 

 

6.3.3 

INSTALLATION 

IP20 protection controllers are designed for installation in an indoor dry environment without aggressive chemicals in normal areas according 
to  ČSN  33  2000-3,  ambient  temperature  up  to  30  °C.  The  short-circuit  resistance  of  the  Digireg

®

 switchboard  is  6  kA. 

Distribution  board 

protection is IP20 or IP65 and the material is listed 

below in the catalog sheets at www.solerpalau.co.uk

Cross-sections of power cables (fans, 

pumps, electric heaters…) must be designed according to specific installation conditions in accordance with 

ČSN 33 2000-5-52 ed.2.

 

The installation must be carried out by an authorized person working on electrical equipment in accordance with legal requirements and familiar 
with the function 

of the individual components of air conditioning and control. Observe the valid ČSN during installation. 

An initial inspection 

must be performed before commissioning. 

For the assembly and installation of air conditioning, an authorized project of air conditioning and 

M&R is required, which solves both the air outputs and the piping system, as well as the electrical connection of elements and operating 
modes.

 

www.solerpalau.co.uk

 

For heat recovery units supplied with a free located Digireg

®

 control box, which is not fixed to 

the unit wall, the firm housing must be ensured of harness between the unit and control box in 
the firm cable line (such as cable trays, cable bench etc.). The harness between the unit and 
the control box shall not be freely suspended or positioned on the floor!!! After firm laying of the 
harness it is possible to start the works on connection of individual wires to the Digireg

®

 

control box. 

!

 

CAUTION!

 

Digireg

®

 distribution boards are not 

designed for direct installation to the 
flammable material!

 

!

 

CAUTION! 

For units with a direct evaporator (marked DX and DXr in the unit 
code),  it  is  possible  to  maintain  the  required  air  temperature  in 
the  room  with  accuracy,  depending  on  the  correctness  of  the 
project  and  the  correct  function  and  setting  of  the  ventilation 
system with accuracy of ±2°C. 

Содержание DUOVENT COMPACT DV

Страница 1: ...INSTRUCTION MANUAL www solerpalau co uk DUOVENT COMPACT DV Ventilation unit with heat recovery...

Страница 2: ...n Connection of electric heater Connection of water heater Connection of water cooler Connection of direct evaporator Connection of condensate drain Bypass and mixing flap Inlet and outlet flap 5 2 10...

Страница 3: ...ation Warranty conditions The device must be installed by a professional air handling service company DUOVENT COMPACTDV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by t...

Страница 4: ...hat could affect safety and proper function are prohibited Installation and operating documentation must be available to the operator and service It is advisable to place it close to the installed uni...

Страница 5: ...nit for ventilation of pool halls Order examples DUOVENT COMPACT DV 3000 DI DX MX KL G4 F7 F7 DVAV JH2 Unit size 3000 with electric heater direct evaporator bypass and mixing flap two stage filtration...

Страница 6: ...INSULATION OF THE ANTIFREEZE PROTECTION CONTACT SENSOR WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNI...

Страница 7: ...0 182 DUOVENT DV 1200 521 992 312 80 2091 260 5 260 5 582 300 500 DUOVENT COMPACT DV 500 to 1200 under ceiling arrangement positions xH AH unit position drawn UNIT BOTTOM VIEW Exchanger outlets UNIT T...

Страница 8: ...2 X3 L Y D Y Exchanger outlets D 20 D 1 2 1 2 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 19 18 18 18 Condensate drains 152 152 152 21 www solerpalau co uk 40 A 150 B A B 150 F 157 42 42 X1 X...

Страница 9: ...94 694 694 627 627 694 694 694 694 694 1085 1085 1085 1085 1085 1085 1085 DUOVENT COMPACT DV 1800 to 7800 floor arrangement positions xP AP unit position drawn X3 X1 X2 X E E X 1 2 1 2 19 18 18 18 Tra...

Страница 10: ...00V 50Hz 3000 1238 927 1 8 1 4 89 1 3500 320 387 3000 DCA DCC 3000 DCA DX 21 8 21 8 21 3 21 3000 DI 15 22 4200 4200 DCA 4200 DCB 4200 DCA DCC 4200 DCA DX 4200 DI 29 8 22 30 2 20 5 29 8 3 400V 50Hz 420...

Страница 11: ...ES EXCHANGER OUTLETS ETC Ensure proper balancing of the transported unit The ropes above the unit must be stretched to prevent damage The outdoor variants of the units are fitted with transport profil...

Страница 12: ...is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate formed in the air duct can in unfavourable conditions spill into the interior of the unit where...

Страница 13: ...tion box 5 1 2 HOW TO STORE THE UNIT AT THE DESTINATION The unit is designed for floor mounting in a vertical position positions marked xV in the unit code or horizontal position positions marked xP i...

Страница 14: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with...

Страница 15: ...let and outlet ports with respect to the position of the exchanger connection pipes Neck variants vertical arrangement viewed from unit operation side INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INL...

Страница 16: ...TLET OUTLET www solerpalau co uk INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET...

Страница 17: ...INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET...

Страница 18: ...n it is exceeded the operating thermostat opens and switches off the heater after cooling below 60 C the heater automatically switches on again Location of the release button under the cover on the un...

Страница 19: ...nger connections it is necessary for example to hold the heat exchanger neck with a second wrench so that the tightening torque is not transmitted to the heat exchanger body Table of dimensions of wat...

Страница 20: ...n screws on the heat exchanger collectors The heat exchanger can then be disconnected from the heating water distribution system and removed from the unit Max operating water temperature of water heat...

Страница 21: ...the cooler must be vented after connecting and filling the system with cooling water The vent screws are located directly at the heat exchanger connection necks The vent screws are accessible either...

Страница 22: ...specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a technician with the appropriate authorization according to the law 5 2...

Страница 23: ...ING FLAP In the basic version each unit is equipped with a bypass flap of the plate heat exchanger BP The bypass is used for summer ventilation defrost control of the recuperation exchanger in the eve...

Страница 24: ...on mode Location of mixing and bypass flap for DUOVENT 500 800 1200 units with MX mixing mode www solerpalau co uk ETA flap Mixing flap MX ODA flap Bypass flap BP Circulation flap C part 1 ODA flap Ci...

Страница 25: ...uators 5 2 10 BASIC ACCESSORIES 5 2 10 1 CONDENSATE DRAIN TRAPS Condensate traps must be ordered as a separate item as they are not included with the unit Vacuum type siphon scheme SF P 300 bottom edg...

Страница 26: ...ected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When placed under the ceiling it is necessary to maintain control an...

Страница 27: ...I C control system to the electrical distribution network is made by a separate supply cable which is not part of the delivery of the device www solerpalau co uk Ventilation unit with heat recovery DU...

Страница 28: ...ts according to the set parameters in the automatic summer winter mode according to the outdoor temperature and time dependencies Manual mode selection is also possible The heater can be hot water con...

Страница 29: ...otation of the fans the correct phasing of the damper actuators and mixing valves If the unit is equipped with a Digireg control system directly from the factory a SETPACK test package has been perfor...

Страница 30: ...onnection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATION The material content of the comprehe...

Страница 31: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with t...

Страница 32: ...NH IH2 JH2 MH2 NH2 263 295 263 365 KH LH OH PH KH2 LH2 OH2 PH2 263 295 263 295 1200 1200 all positions 420 365 365 420 ETA filter size ETA mm ODA filter size ETA mm Size of DUOVENT DV Vnom m3 h Neck...

Страница 33: ...replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove the fan as shown in the following figure K...

Страница 34: ...nitor the implementation of the measures taken Check the siphons for condensate drainage especially their permeability and tightness especially the tightness of the mounting on the unit and the tightn...

Страница 35: ...l applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be a...

Отзывы: