The following table shows the mode to proceed to detect and resolve any incidents shown:
Alarm
number
Alarm text
Description
Type
1
Run Error Supply Air Fan
Malfunction of supply air fan
A
2
Run Error Extract Air Fan
Malfunction of extract air fan
A
6
Change ODA Filter
Outdoor Air Filter needs replacement
C
11
Remote off active
Remote On/Off active
C
23
Electric heating is overheated
Electric Heater Thermal protectors activated
A
24
Frost risk
Frost protection function is overriding the control of
the water heater output
C
25
Water temp too low, system off
Water temperature below frost limit value (<7ºC)
C
27
Sensor error outdoor temp.
Malfunction of outdoor air temperature sensor
A
28
Exchanger frost risk
Exchanger deicing activated
C
41
Manual heater control
The electric heater is in manual mode
C
42
Manual heater control
The resistance is in manual mode
C
48
Internal battery error
The electric heater is in manual mode
A
49
Sensor error Supply Air temp
Malfunction of supply air temperature sensor
A
50
Sensor error Extract Air temp
Malfunction of extraction air temperature sensor
A
55
Sensor error SAF pressure
Malfunction of supply air pressure sensor
A
56
Sensor error EAF pressure
Malfunction of exhaust air pressure sensor
A
57
Sensor error Exhaust air temp
Malfunction of exhaust air temperature sensor
A
58
Sensor error Frost Protection temp
Malfunction of water temperature sensor
A
90
Change ETA Filter
Extraction Air Filter needs replacement
C
Содержание CADB/T-HE PRO-REG Series
Страница 1: ...CADB T HE PRO REG EN...
Страница 2: ......
Страница 48: ...48 ENGLISH 16 3 1 Controller recon guration required to manage coil module BA AF HE only as cooling coil...
Страница 63: ...63 23 WIRING DIAGRAMS 23 1 MAIN UNIT...
Страница 64: ...64...
Страница 65: ...65...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68...
Страница 69: ...69...
Страница 70: ...70 23 2 REWIRING TO MANAGE EXTERNAL MODULES Accessories...
Страница 71: ...71...