Off: stop the unit.
Manual Reduced pressure / Manual Normal pressure: Setting manually selection.
Auto: Selection of set point is done according to time programming (see Programme schedule
section).
Advanced level
Occasionally, depending on the characteristics of the duct net (length and diameter) and also
depending on regulating elements (type of dampers and opening / closing times), It may be
necessary to modify the fans speed control output (Proportional and Integral bands).
To modify the proportional and integral bands, from the advanced parameters menu follow the
following sequence:
1- Access to system level
Temperature
Air control
Time sengs
Access rights
Log on
Log off
Change password
Log on
Enter password****
Actual level: None
Log on
Enter password ****
Actual level: None
Log on
Enter password ****
Actual level: Admin
Log on
Log off
Change password
To modify value
To change of digit
2- Adjust the COP parameters
Manual/Auto
Sengs
Configuraon
Access Rights
Temperature control
Pressure control
Alarm sengs
Pressure Ctrl. Supply
P.Band: 1000.0Pa
Acc-I: 20.0 s
Min.output: 20%
Change
parameters
Change
parameters
Pressure Ctrl. Supply
P.Band: 1000.0Pa
Acc-I: 20.0 s
Min.output: 20%
Содержание CADB/T-HE PRO-REG Series
Страница 1: ...CADB T HE PRO REG EN...
Страница 2: ......
Страница 48: ...48 ENGLISH 16 3 1 Controller recon guration required to manage coil module BA AF HE only as cooling coil...
Страница 63: ...63 23 WIRING DIAGRAMS 23 1 MAIN UNIT...
Страница 64: ...64...
Страница 65: ...65...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68...
Страница 69: ...69...
Страница 70: ...70 23 2 REWIRING TO MANAGE EXTERNAL MODULES Accessories...
Страница 71: ...71...