10.2.2. Variable airfl ow operation (VAV)
Mode recommended in single area confi guration for variable airfl ow applications depending
on a signal type 0-10v.
The set point value depends on a signal 0-10 V coming from an outdoor probe (CO
2
, tempera-
ture, relative humidity, etc.) or a manual percentage. The ratio between the fans is entered in
the form of a discharge/supply percentage.
Functional parameter setting:
Access to the simplifi ed parameter setting menu (via the password 1111) allows:
• The selection of the usage range of the signal 0-10V (see example below).
• The variation range of the supply fan’s speed.
• The percentage applied to the discharge with respect to the supply.
Usage example:
Connection of a CO
2
probe of
a measurement range 0-2000
ppm (0-10V). Speed minimum
(25%) below 400 ppm and
maximum (100%) over 1600
ppm
Vmin = 2 V (400ppm)
Vmax = 8V (1600 ppm)
Speed at Vmin = 25%
Speed at Vmax = 100%
The selection of VAV mode in this installer menu automatically confi gures the screen of the
user menu. The user can then change the unit’s operation without touching the settings.
Off: Stop the unit.
Manual: Manually selection of fan’s speed.
Auto: Automatic control according to external probe.
Содержание CADB-N 05 PRO-REG
Страница 2: ......
Страница 15: ...15 ESPA OL Versi n DI con by pass Versi n DC con by pass Accesorio Accesorio Accesorio...
Страница 49: ...49 ENGLISH DI Version with By pass DC Version with By pass Accessory Accessory Accessory...
Страница 116: ...116 NEDERLANDS DI Version met By pass DC Version met By pass Accessoire Accessoire...
Страница 137: ...137 21 ESQUEMAS EL CTRICOS WIRING DIAGRAMS SCHEMAS DE C BLAGE BEDRADINGSSCHEMA...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 141: ...141...
Страница 142: ......
Страница 143: ......