13. WATER HEATER FROST PROTECTION
In models with Water Heater, the temperature of the water return is continually supervised by a probe,
in order to prevent it to freeze.
In case water temperature drops below 12°C, the water valve starts to open (if it already wasn’t) and
Frost Risk alarm is activated.
If water temperature falls below 7°C, then fans are stopped and the alarm
Water temp too low, system
off is activated. Till the temperature is not over 7°C, the unit will not turn on again.
Unit in OFF mode
When the unit is OFF, antifrost protection remains active trying to maintain a constant return water
temperature of 25°C.
14. FROST PROTECTION OF THE HEAT EXCHANGER
In case the exhaust air temperature drops below 5°C, the bypass will open to prevent the freezing of
the exchanger.
In the case that the inlet temperature (Outdoor air) goes down to -7ºC, the supply fan will stop.
15. AIRFLOW MEASUREMENT – CHANGE OF COEFFICIENT K (only operation mode CAV)
In order to obtain the actual fl ow by means of the pressure transmitter, the parameter K has to be
defi ned. It depends on the Heat Recovery Unit model as showed in the following table:
Model
Coeffi cient K
CADB-N 05
58
CADB-N 08
60
CADB-N 18
84
CADB-N 30
131
CADT-N 45
104
CADT-N 55
207
CADT-N 80
252
Содержание CADB-N 05 PRO-REG
Страница 2: ......
Страница 15: ...15 ESPA OL Versi n DI con by pass Versi n DC con by pass Accesorio Accesorio Accesorio...
Страница 49: ...49 ENGLISH DI Version with By pass DC Version with By pass Accessory Accessory Accessory...
Страница 116: ...116 NEDERLANDS DI Version met By pass DC Version met By pass Accessoire Accessoire...
Страница 137: ...137 21 ESQUEMAS EL CTRICOS WIRING DIAGRAMS SCHEMAS DE C BLAGE BEDRADINGSSCHEMA...
Страница 138: ...138...
Страница 139: ...139...
Страница 140: ...140...
Страница 141: ...141...
Страница 142: ......
Страница 143: ......