background image

Installation on S&C Mounting Pedestals

Installing the Pole-Unit

Repeat Steps 27 through 34 for each pole-unit.

Step 27

Remove the pole-unit from the shipping crate 
and lift it, using the following procedure:

Ç

 CAUTION

Lift the pole-unit only by the lifting bracket . 

Lifting it by any other means can dam-

age the pole-unit.

Wrap a hoist sling or other lifting device 

around the lifting bracket at the top of the pole-
unit. Carefully pull the pole-unit upward. The 
foam wrappings around the top, mid-section, 
and base should come off as the pole-unit is 
lifted. Remove these wrappings if they do not 
come off. Do not remove the shipping brace at 
this time. See Figures 26, 27, and 28.

Ç

 CAUTION

DO NOT remove the shipping brace around 
the base of the pole-unit at this time . 

Damage to the operating shaft can 

occur.

Figure 26. Lift the pole-unit only by the lifting bracket.

Pole-unit

Lifting bracket

Figure 27. Pull the pole-unit carefully upward.

Figure 28. Do not remove the shipping brace at this time.

Pole-unit

Shipping brace

S&C Instruction Sheet 731-502

  17

Содержание Trans-Rupter II SE

Страница 1: ...inet Set Up Connecting Current Transformers to the Control Cabinet 27 Testing Control Devices 28 Installing Optional Bypass Accessory Before Starting 32 Operation 33 Terminal Pad and Conductor Connect...

Страница 2: ...CAUTION The equipment in this publication is only intended for primary side application on distribution substation transformers The application must be within the ratings fur nished for the equipment...

Страница 3: ...NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portio...

Страница 4: ...afety Alert Message Description Part Number A WARNING Do not close Trans Rupter II if the source side series disconnect is closed G 7016R1 B WARNING Do not charge if disconnect is closed G 7009 1 C WA...

Страница 5: ...three pole units a control cabinet a manual charging tool and six terminal pads and their associated hardware Pole units are shipped fully pressurized at 75 psig The pole units and charging tool are...

Страница 6: ...rate and lift it using the following procedure CAUTION Lift the pole unit only by the lifting bracket Lifting it by any other means can dam age the pole unit Wrap a hoist sling or other lifting device...

Страница 7: ...Installation on a User Furnished Structure Figure 2 Pull the pole unit carefully upward Figure 3 Do not remove the shipping brace at this time Pole unit Shipping brace S C Instruction Sheet 731 502 7...

Страница 8: ...d the pole unit lifted off the ground check that the gas pressure gauge on the underside of the pole unit base is in the OK to operate zone See Figures 4 and 5 NOTICE The gas pressure gauge needle sho...

Страница 9: ...can be mounted in one of four positions located 90 apart Determine where terminal pads will be attached before mounting the pole unit Step 5 Remove the shipping brace from the pole unit base See Figur...

Страница 10: ...ling or lifting device from the pole unit at this time See Figure 8 Figure 8 Attach the pole unit base to the bracket Top and bottom mounting boss locations Mounting bracket Pole unit base Step 7 Atta...

Страница 11: ...UTION Two sets of mounting bosses positioned 180 apart must be used to mount the pole unit If the correct mounting bosses are not used the pole unit will not be ade quately supported and the pole unit...

Страница 12: ...Then bolt all four tabs to the mounting structure using user furnished C inch hardware See Figure 13 Figure 13 Bolt the tabs of the control cabinet to the mounting structure Mounting structure Top mo...

Страница 13: ...her location Figure 16 Remove the three removable screws at each pole unit electrical junction box cover Loosen the fourth retaining screw Window bolts DO NOT REMOVE Retaining screw Cover Removable sc...

Страница 14: ...hole s along the bottom of the con trol cabinet See Figure 18 Figure 18 Attach the conduit to the hole s along the bottom of the connection enclosure Conduit Step 17 Following the wiring diagram furn...

Страница 15: ...for the connection enclosure face the desired direction per the catalog drawing b Adjust the lower set of anchor bolt nuts to generally plumb and level the pedestals The upper set of anchor bolt nuts...

Страница 16: ...arm attachment brackets using the B 1131Z x bolts furnished Fully tighten the bolts e Using a level verify that the cross base is horizontal both lengthwise and side to side Adjust the anchor bolts as...

Страница 17: ...fully pull the pole unit upward The foam wrappings around the top mid section and base should come off as the pole unit is lifted Remove these wrappings if they do not come off Do not remove the shipp...

Страница 18: ...he pole unit lifted off the ground check that the gas pressure gauge on the underside of the pole unit base is in the OK to operate zone See Figures 29 and 30 NOTICE The gas pressure gauge needle shou...

Страница 19: ...where the conduit will be attached See Figure 31 Step 30 Remove the shipping brace from the pole unit base See Figure 32 CAUTION DO NOT rest the pole unit on its base after the shipping brace has been...

Страница 20: ...osses must be used Screw each stud until it bottoms approxi mately 8 to 9 turns DO NOT remove the hoist sling or lifting device from the pole unit at this time See Figure 34 Figure 33 Place the pole u...

Страница 21: ...ng or lifting device from the pole unit Figure 35 Tighten the nuts Pole unit base Mounting bracket Cross base Pedestal Tabs Tabs Figure 36 Bolt the tabs of the control cabinet to the pedestal Mounting...

Страница 22: ...onal area to the flange at the bottom rear of the enclosure Flange Base of control cabinet Figure 38 If additional holes for control wiring are required remove the conduit entrance plate and punch the...

Страница 23: ...y in the hooks at the top of the pedestals Conduit assembly Pedestal hooks Figure 41 Using the offset mounting brackets attach the conduit assembly to the pedestal Offset mounting bracket Conduit asse...

Страница 24: ...22 AWG wire Use of 18 gauge wiring is recommended NOTICE To ensure proper crimping of the butt splices use the Panduit controlled cycle hand tool CT 1550 or equivalent for attaching 18 to 20 gauge in...

Страница 25: ...eyed to the female socket See Figure 45 Push the plug into the socket and turn the black ring until the red line around the outside of the socket is obscured See Figures 46 and 47 Figure 47 Quick conn...

Страница 26: ...tep 47 Connect the pole unit wiring and user furnished control circuit wiring to the appropriate termi nation blocks in the control cabinet in accor dance with the wiring diagram furnished See Figure...

Страница 27: ...protection system may not function properly Step 48 Following the wiring diagram furnished con nect user furnished current transformers CTs to the shorting blocks in the control cabinet Follow standar...

Страница 28: ...Guide the hooked end of the charging tool between the ears of the pole unit operating shaft and engage the operating shaft pin See Figures 51 52 and 53 CAUTION Use only the manual charging tool provid...

Страница 29: ...to reset the pole unit mechanism See Figure 55 Approxi mately 40 revolutions are needed Keep turning until the internal stop is reached Then remove the charging tool CAUTION The charging tool must be...

Страница 30: ...600 mA input current the trip energy supply will charge in approximately 3 seconds Use a user furnished secondary current injection kit as follows a If an optional test switch is furnished remove the...

Страница 31: ...rol Cabinet Set Up Step 53 To initiate a trip operation inject secondary current into the relay Refer to the relay manu facturer s instructions Verify that the trip energy supply is storing energy Ope...

Страница 32: ...nduc tors terminal pads and associated hardware Step 54 Thoroughly clean the surface of the Trans Rupter II casting and the surface of the bypass accessory terminal pads using a soft cloth Immediately...

Страница 33: ...nter line of the contact fingers See Figure 63 If the blade assembly needs adjustment loosen the hinge support and blade stop bracket hardware See Figure 64 Center the blade between upper contact fing...

Страница 34: ...sing the Z x 1331 hex head stainless steel cap screws and Z x inch stainless steel lockwashers furnished attach the upper and lower terminal pad to the appropriate set of tapped holes on the pole unit...

Страница 35: ...d in any posi tion Test for voltage using proper high voltage test equipment and install suitable grounding equipment Failure to observe these precautions may result in serious injury or death Repeat...

Страница 36: ...e See Figure 69 The pins for CT shorting blocks are removed See Figure 70 Refer to the relay manufacturer s instruc tions for set up and testing procedures for the relays Figure 68 Make sure all three...

Страница 37: ...and the insulated shaft Linchpin Figure 72 Pull the tool handle and the insulating shaft apart Linchpin Tool handle Insulating shaft NOTICE To prevent excessive wear or corrosion store the Trans Rupt...

Страница 38: ...t Tool head Figure 75 Push the tool head and the insulating shaft together Assembling the Charging Tool Step 68 Push the tool head and the insulating shaft together Align the holes on the tool head an...

Страница 39: ...s for the Charging Tool Extra sections can be assembled in accordance with the instructions above It is recommended that a maximum of two 48 inch sections be added to the tool Figure 77 Push the handl...

Страница 40: ...the indicator reads CLOSED See Figure 80 CLOSED and charged Figure 80 The pole unit is CLOSED and charged The indicator reads CLOSED Figure 81 Gauge needle in white OK to operate zone OK to operate z...

Страница 41: ...inimum functional level and the pole unit will not maintain full interrupting or dielectric ratings The pole unit should be removed from service and replaced promptly Do not operate this Trans Rupter...

Страница 42: ...gas den sity in the pole unit has dropped below the minimum functional level The pole unit will not maintain full interrupting or dielectric ratings The pole unit should be removed from service and re...

Страница 43: ...es Check that the red LED is flashing See Figure 86 That the trip energy supply is storing energy Open the swingout panel to access the cir cuit board of the trip energy supply Press the push button o...

Страница 44: ...r s instruc tions for recommendations on testing and inspection of the relays Guidelines for Interrupter Resistance Values Trans Rupter II interrupters should have resis tance values under 200 micro o...

Отзывы: