36
S&C Instruction Sheet 653-506
Annual Maintenance
DANGER
The PureWave UPS System must be disabled, placed in the
Bypass Isolate state, and
be de-energized before performing maintenance on the equipment . Failure to do so can
result in serious injury or even death .
Maintenance should only be conducted by S&C Electric Company personnel or
personnel who are properly trained by S&C Electric Company.
Preparation
q
Review the steps in this procedure to prepare the proper tools and test equipment that
will be needed to complete the tasks.
q
Bring site-specific schematics and familiarize yourself with when and how you will isolate
the circuits during the maintenance.
q
Coordinate with the site facilitator to obtain keys for locks (if applicable) to unlock the
doors to the PureWave UPS System enclosure(s).
q
Confirm with the site facilitator that the PureWave UPS System is de-energized.
Verified By:_________________________ Date: ___________
Required Tools
q
Shop vacuum
q
Rags or paper towels
q
General purpose cleaner (e.g. Simple Green)
q
Personal protective equipment
q
Insulated torque wrench
q
Standard assorted insulated hand tools (wrench, flat-head screwdriver, etc.)
q
DAP concrete sealant
q
PureWave UPS enclosure touch-up paint
q
Lock-out/Tag-out tags and locks
q
Calibrated Hioki 16 Channel Digital Waveform Recorder or oscilloscope
q
Two calibrated Fluke 87 digital multimeters
Verified By:_________________________ Date: ___________
Arrival
q
Jobsite name:
q
Discuss maintenance plan with the local jobsite facilitator.
Record the following information:
q
System state: _______________________________
q
List any active alarms: _______________________________________
Verified By:_________________________ Date: ___________
Maintenance