26 S&C Instruction Sheet 1023-550
Temperature Sensor O.K.
A problem with the temperature sensor has cleared.
Voltage Override Active
A high-voltage or low-voltage condition is present. See Instruction Sheet 1023-530, “S&C
IntelliCap® Plus Automatic Capacitor Control:
Setup
,” for more information.
Voltage Override Cleared
A high-voltage or low-voltage condition has cleared.
Voltage Sensor Bad
The voltage sensor is reading outside of its range or may be faulty. If the sensor reading is
out-of-range on the high end while the control is in
Automatic
mode, the control switches
the capacitor bank open.
Voltage Sensor O.K.
A problem with the voltage sensor has cleared.
For controls with var sensing, there are two additional event messages:
Reverse Current Detected
The capacitor control has detected a reverse-current condition.
Reverse Current Cleared
A reverse-current condition has cleared.
For controls with neutral sensing the additional event messages are:
Neutral Sensor Alarm Active
The level of neutral current or neutral voltage has caused the
Neutral Sensor
alarm
to trigger. See Instruction Sheet 1023-530, “S&C IntelliCap® Plus Automatic Capacitor
Control:
Setup
,” and Instruction Sheet 1023-540, “S&C IntelliCap® Plus Automatic
Capacitor Control:
Operation
,” for more information.
Neutral Sensor Alarm Cleared
The
Neutral Sensor
alarm has cleared.
Neutral Sensor Alarm Retry Cleared
The
Neutral Sensor
alarm retry has cleared.
Neutral Sensor Alarm Retry Pending
The
Neutral Sensor
alarm retry is pending.
Neutral Sensor Alarm Subsequent Retry Completed
The
Neutral Sensor
alarm subsequent retry has completed.
Neutral Sensor Alarm Subsequent Retry Pending
The
Neutral Sensor
alarm subsequent retry is pending.
Neutral Sensor Lockout
Neutral current has caused lockout.
Reset Neutral Sensor Lockout
The neutral sensor lockout has been reset.
Using IntelliLink Software to Locate Problems